RC24V v.1.0 Battery controller 24VDC/10A for RACK 19" cabinets EN Edition: 1 from 09.02.
www.pulsar.pl RACK POWER RC24V The battery controller features: Microprocessor-based automation system Automatic battery test every 5 min.
www.pulsar.pl RC24V RACK POWER 1. Technical description. 1.1. General description. The RC24V battery controller is designed for monitoring the status of the 2÷4 battery pack based (the total capacity of 80Ah/12V (SLA) max. batteries), on the measurements of resistance, continuity of the battery circuit, voltage, and the charge level. It is also protected against reverse connection and short circuit in the charging circuit.
www.pulsar.pl RACK POWER RC24V Fig. 2. General view. 1.4. Technical parameters. - Electrical parameters (Table 2) - Mechanical parameters (Table 3) - Operation safety (Table 4) - Operation parameters (Table 5) Electrical parameters (Table 2).
www.pulsar.pl RACK POWER RC24V Operation parameters (Table 4). Environmental class Operation temperature Storage temperature Relative humidity Sinusoidal vibrations during operation: Surges during operation Direct insolation Vibrations and surges during transport 2. Installation. II -10ºC...+40ºC -20ºC...+60ºC 20%...90%, no condensation Unacceptable Unacceptable Unacceptable According to the PN-83/T-42106 standard 2.1. Requirements.
www.pulsar.pl RACK POWER RC24V 2. Indication of operation of the battery controller. 3.1. Optical indication. The controller is equipped with LED light at the front panel: RED LED: ON/blinking – Indicates a failure (Table 6) OFF – No errors/normal operation 3.2. Technical output. The controller is fitted with the ALARM technical output of collective failure. The collective failure can be triggered by the events presented in Table 6. Fig. 6.
www.pulsar.pl RC24V RACK POWER 4. Maintenance and operation. 4.1. Automatic battery test The battery controller performs a battery test every 5 minutes, temporarily stopping the charge process, while measuring voltage at the battery terminals and the resistance of the battery circuit. The test can also be started manually by pressing the "TEST" button on the front panel, but not more often than once every 1 minute. The activation or deactivation of the test will be confirmed acoustically (see Table 6).
www.pulsar.pl RACK POWER RC24V WEEE LABEL Waste electrical and electronic equipment must not be disposed of with normal household waste. According to the European Union WEEE Directive, waste electrical and electronic equipment should be disposed of separately from normal household waste. The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law.