RC12V v.1.0 Battery controller 12VDC/20A for RACK 19" cabinets EN Edition: 1 from 09.02.
www.pulsar.pl RACK POWER RC12V The battery controller features: Microprocessor-based automation system Automatic battery test every 5 min.
www.pulsar.pl RC12V RACK POWER 1. Technical description. 1.1. General description. The RC12V battery controller is designed for monitoring the status of the 1÷4 battery pack based (the total capacity of 84Ah/12V (SLA) max. batteries), on the measurements of resistance, continuity of the battery circuit, voltage, and the charge level. It is also protected against reverse connection and short circuit in the charging circuit.
www.pulsar.pl RACK POWER RC12V Fig. 2. General view. 1.4. Technical parameters. - Electrical parameters (Table 2) - Mechanical parameters (Table 3) - Operation safety (Table 4) - Operation parameters (Table 5) Electrical parameters (Table 2).
www.pulsar.pl RACK POWER RC12V 2. Installation. 2.1. Requirements. The enclosure should be mounted by a qualified installer, holding relevant (applicable and required for a given country) permits and licenses for low-voltage installations. The device shall be mounted in confined spaces (in accordance with the 2nd environmental class) with normal air humidity (RH=90% max. without condensation) and the temperature from -10°C to +40°C.
www.pulsar.pl RACK POWER RC12V 3. Indication of operation of the battery controller 3.1. Optical indication. The controller is equipped with LED light at the front panel: RED LED: ON/blinking – Indicates a failure (Table 6) OFF – No errors/normal operation 3.2. Technical output. The controller is fitted with the ALARM technical output of collective failure. The collective failure can be triggered by the events presented in Table 6. Fig. 6.
www.pulsar.pl RC12V RACK POWER 4. Maintenance and operation. 4.1. Automatic battery test The battery controller performs a battery test every 5 minutes, temporarily stopping the charge process, while measuring voltage at the battery terminals and the resistance of the battery circuit. The test can also be started manually by pressing the "TEST" button on the front panel, but not more often than once every 1 minute. The activation or deactivation of the test will be confirmed acoustically (see Table 6).
www.pulsar.pl RACK POWER RC12V WEEE LABEL Waste electrical and electronic equipment must not be disposed of with normal household waste. According to the European Union WEEE Directive, waste electrical and electronic equipment should be disposed of separately from normal household waste. The power supply unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law.