User Instructions
www.pulsar.pl R1612T RACK POWER
5
1.4. Specifications.
- electrical parameters (tab.2)
- mechanical parameters (tab.3)
- operation safety (tab.4)
- operating parameters (tab.5)
Electrical parameters (tab. 2).
Mains supply
176÷264V AC
Current up to
1,6A@230V AC max.
Supply power
168W max.
Efficiency
80%
Output voltage
12V DC
Voltage adjustment range output
12÷15V DC
Output current
16 x 0,87A (I = 14A) max. @12V
Ripple
100 mV p-p max.
Short-circuit protection SCP
16 x F 1,5A melting fuse
Overload protection OLP
105% ÷ 150% of the PSU power, automatic return
Overvoltage protection OVP
>16V (automatic recovery)
Surge protection
varistors
Optical indication of operation:
LED: AC, DC, TEMP, LoB, ALARM, AUX1÷AUX16
Acoustic operation indication:
Piezoelectric indicator ~75dB/0,3m
The ALARM technical output of collective failure
Relay type: 1A@ 30VDC/50VAC
The F
MAINS
fuse in the 230V power supply circuit
T 3,15A
F1÷F16 fuses in the camera power supply
circuits AUX(+)
F 1,5A
Mechanical parameters (tab. 3).
Enclosure dimensions
W=19”, H=2U; 482 x 88 x 223 mm (WxHxD)
Fixation
four-point butt mounting to RACK profiles – the set include 4 M6 screws + cage nuts
Net weight
5,6kg / 6kg
Enclosure
Steel plate RAL 9005, black
Connectors
230V AC input: the IEC C14 socket with a fuse, power cable 1,5m
(included)
Outputs: ALARM, AUX1÷AUX16: Φ0,5-2,1 (AWG 24-12) 0,5-2mm
2
Notes
Forced cooling (fan)
Operation safety (tab.4).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.5).
Environmental class
II
Operating temperature
-10ºC...+45ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1. Requirements.
The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall
be mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max.
without condensation) and the temperature from -10°C do +45°C.