User Instructions
www.pulsar.pl PSCU 04344SEP
5
Electrical parameters (Table 3)
Supply voltage
230V AC
Current consumption
0,8A@230V AC max.
PSU’s power
120W max.
Output voltage
30V÷ 35V DC (100% load ÷ 0% load)
Output current
4x1A@30V DC max.
Short-circuit protection SCP
4x T 1A melting fuse (failure requires fuse replacement)
Overload protection OLP
DC 30V: 4 x T 1A circuit
AC 230V: T 3,15A circuit
Surge protection
varistors
Mechanical parameters (Table 4)
Dimensions
W=270, H=150, D+D
1
=72 +8 [+/- 2 mm]
W
1
=275, H
1
=154 [+/- 2 mm]
Mounting
see Fig. 3
Battery housing
2,7kg / 2,8kg
Net/gross weight
Steel plate, DC01 1,0mm color RAL 9003
Enclosure
Cylindrical screw (at the front)
Terminals
Mains supply: Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,51-2,05 (AWG 24-12)
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.
Safety of use (Table 5)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operation parameters (Table 6)
Environmental class
II
Operating temperature
-10ºC...+40ºC
Storing temperature
-20ºC...+60ºC
Relative humidity
20%...90%, no condensation
Vibrations during operation
unacceptable
Surges during operation
unacceptable
Direct insolation
unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard