6.2.3 Battery protection ON/OFF.
This function enables or disables the battery protection against excessive discharge UVP (see section 7.2).
- use the „>” or „<” buttons to display the Battery protect. menu
- press the „SET” button, the prompt will appear at the end of the line
- use the „<” or „>” buttons to choose
ON – battery protection (disconnection) ON
OFF – battery protection (disconnection) OFF
- confirm by pressing the „SET” button
6.2.4 Setting the delay time for EPS output indicating ~230 V power loss.
The PSU features adjustable delay for 230 V power loss indication. The delay time can be selected from
the four available ranges:
- 5s (factory setting)
- 2min 20s
- 17min
- 2h 20min
230 V power loss is indicated by the activation of the “EPS FLT” technical output.
- use the „<” or „>” buttons to display the Delay time for EPS output menu
- press the „SET” button, the prompt will appear at the end of the line