User Instructions

www.pulsar.pl PSBEN5012D/LCD BLACK POWER
41
real time clock with battery backup
Acoustic indication:
- piezoelectric indicator ~75 dB /0,3 m, switchable via jumper
LCD screen battery
3 V lithium battery, CR2032
F
BAT
fuse
F
MAIN
fuse
T 6,3 A / 250 V
T 3,15 A / 250 V
Additional accessories (not included)
- RS485 ‘INTR’ interface: RS485 communication
- Ethernet ‘INTE’ interface; Ethernet communication
- RS485-Ethernet “INTRE’ interface; RS485-Ethernet
communication
Table 17. Mechanical parameters.
Dimensions
W=330, H=350, D+D
1
=173+8 [+/- 2mm]
W
1
=335, H
1
=355 [+/- 2mm]
The dimensions of the battery
compartment
205 x 165 x 165mm (WxHxD) max
Mounting
See Fig. 3
Net/gross weight
7,6/8,7 kg
Enclosure
Steel plate DC01 1mm, color RAL 9005 (black)
Closing
Cheese head screw x2 (at the front), lock assembly possible
Terminals
Supply: Φ0,63÷2,50 (AWG 22-10)
Outputs: Ф0,51÷2 (AWG 24-12), BAT battery outputs: 6,3F-2,5, 30cm
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Table 18. Safety of use.
Protection class EN 60950-1:2007
I (first)
Protection grade EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC