User Instructions

4
3. Cooperation with the MPSB48 automation module (option).
The MPSB48 automation module is intended for indicating the operating status of buffer power supplies, PSB 54V
type. The PCB board features LEDs that indicate PSU operating status (presence of AC voltage, presence of DC voltage,
battery voltage). The module is also equipped with technical outputs of: EPS - AC power loss, PSU - PSU failure, LoB -
low battery voltage.
Element no.
Description
[1]
LED indicating presence of AC power
[2]
LED indicating presence of DC power
[3]
LED indicating correct battery voltage
[4]
EPS - AC absence technical output relay type
[5]
PSU - output indicating DC absence/PSU failure relay type
[6]
LoB - output indicating battery low voltage relay type
[7]
EPS - AC absence technical output OC type
[8]
PSU - output indicating DC absence/PSU failure - OC type
[9]
LoB - output indicating battery low voltage - OC type
[10]
+V ,-V- DC supply output
[11]
L-N 230V/AC power connector, PE protection connector
[12]
Connector of extra LED indication
[13]
Battery connectors: +BAT =red, - BAT = black
[14]
V
ADJ
- potentiometer, DC voltage adjustment
Fig. 3. The view of the PSU with the MPSB48 module.
4. Maintenance.
All maintenance procedures can be performed after the disconnection of the power supply from the electrical grid.
The power supply does not require any special maintenance procedures, but in the case of significant dust accumulation,
dusting using compressed air is recommended.
Pulsar sp. j.
Siedlec 150, 32-744 Łapczyca, Polska
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
WEEE MARKING
According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste and to collect such
WEEE separately.