Operating instructions
www.pulsar.pl       POE084824B  GREEN POWER CCTV PoE 
5
W
H
D
Output current
t
AMB
<30°C
8
x 0,3
A 
–
see diagram
1
Output current
t
AMB
=40°C
8
x 0,21A 
–
see diagram
1
Ripple voltage   240 mV p-p max. 
Battery charging current  0,16A 
Current consumption by the PSU  0,2A max. @ 4x7Ah (± 5%) 
Short-circuit protection SCP  PoE MODULE 
8 x F 0,5A or 8 x PTC 0,5A (jumper selectable) 
PSU MODULE 
105% ÷ 150% of PSU power, electronic current limiting 
Overload protection OLP  105% ÷ 150% of PSU power, electronic current limiting 
Battery circuit protection SCP and reverse 
polarity connection 
melting fuse 
Overvoltage protection OVP  62,1÷72,9V DC 
Deep discharge battery protection UVP  U<37 V (± 5%) – disconnecting the battery terminal 
Surge protection  8 x varistor 
Antisabotage protection: 
- TAMPER output indicating enclosure opening 
- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 
Optical indication of operation:  YES – LED lights  
Technical outputs: 
- FPS technical output indicating output fuse 
activation 
- OC type, 50mA max. 
Normal operation:  L state (0V), 
failure: H state (hi-Z), (automatic return once the normal 
operation is restored) 
- relay type: 1A@ 30VDC/50VAC, delay time: 
approximately 10 seconds 
F1 ÷ F8 fuses  F 0,5A or PTC 0,5A 
 Mechanical parameters (Table 4). 
Enclosure dimensions  300 x 407 x 126 mm (WxHxD) 
Mounting  See Fig. 3 
Battery housing: 
4x7Ah/12V (SLA) max. 
250x 165x105mm (WxHxD) max 
Net weight  5,1kg / 5,4kg 
Enclosure  DC01 steel plate, 1,0mm, RAL 9003 
Closing  Cylindrical screw x 2 (at the front) lock assembly possible 
Terminals  Switch mode power supply: Φ0,4-2,5 (AWG 26-10) 
PoE module: Φ0,5-2,1 (AWG 24-12) 
AUX1...8 outputs: RJ45 8pin 
TAMPER output: Φ0,8 
Notes  The enclosure has a 15mm distance from the mounting surface so the cables 
can be led. 
 Safety of use (Table 5). 
Protection class PN-EN 60950-1:2007  I (first) 
Protection grade PN-EN 60529: 2002 (U)  IP20 
Insulation electrical strength: 
- between input (network) circuit and the output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 
3000 V/AC min. 
1500 V/AC min. 
 500 V/AC min. 
Insulation resistance: 
- between input circuit and output or protection circuit 
100 MΩ, 500V/DC  
Operation parameters (Table 6). 
Operating temperature  -10ºC...+40ºC (see Figure1) 
Storing temperature  -20ºC...+60ºC 
Relative humidity  20%...90%, no condensation 
Vibrations during operation   unacceptable 
Surges during operation  unacceptable 
Direct insolation  unacceptable 
Vibrations and surges during transport  According to the PN-83/T-42106 standard 