Replacement Part List

All loads MUST be disconnected from the generator. Never start or stop the engine with electrical devices plugged in to
the receptacles.
Turn the engine switch to the Stop position.
Turn the fuel valve to the “OFF” position.
Receptacles and Extension Cords
Only use high quality, well-insulated, grounded extension cords in good condition with generator receptacles. Extension
cords should have a minimum rating of 125 Volts AC, 20 Amps and should be kept as short as possible to minimize voltage
drop. Follow each load manufacturer’s power rating recommendation when selecting receptacle and extension cord.
This generator is equipped with the following receptacles:
120 Volt AC, 20 Amp receptacle
Four 120 Volt AC, 20 Amp receptacles.
One 120 Volt AC, Twist-Lock outlet.
120 / 240 Volt AC, 30 Amp twist lock receptacle (NEMA L14-30).
This receptacle has a 20 Amp push-to reset circuit breaker to protect against overload.
Each socket is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 2400 watts (2.4 kW) at 20 Amps.
Use extension cords having a minimum rating of 125 Volts AC, 20 Amps.
How to Stop Engine (See fig 12-14)
Fig 12 Fig 13 Fig 14
OPERATION
This receptacle has a 30 Amp push-to reset circuit breaker to protect against overload.
This receptacle is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 3600 watts (3.6 kW) at 30
Amps. It is also rated to operate 240 Volt AC, single phase, 60Hz loads requiring up to 7,200 watts (7.2 kW).
Use a NEMA L14-30 plug with this receptacle.
Use a 4-wire cord rated for 240 Volts AC, 30 Amps to the plug. You can use the same 4-wire cord to operate a 120 Volt
load.
120 / 240 Volt AC, 30 Amp locking receptacle
Do not connect 3-phase loads to generator.CAUTION!
16
One 120/240 Volt AC,50Amp RV receptacle
NEMA
L5-30
120/240V 50 A 120/240V 30 A 120V 30 A
120V 20 A 120V 20 A
PUSH
START
RUN
STOP
PUSH BUTTON
AUTOMATIC
TRANSFER SWITCH
V.F.T. METER
MAIN
BREAKER
AC
BREAKER
AC
BREAKER
AC
BREAKER
AC
BREAKER
AC
BREAKER
STOP