Full Product Manual
6
Installation (cont’d)
Supporting and Mounting 
Mount the generator on a concrete slab capable of supporting the weight of the generator. The 
slab must extend on all sides beyond the frame by at least one foot. Contact a cement contractor 
for slab specifications if necessary. Attach the frame to the concrete slab using 3/8” diameter 
expansion anchor bolts (not supplied).
Grounding
  NOTE: IT IS RECOMMENDED THAT ONLY A TRAINED AND LICENSED   
  ELECTRICIAN PERFORM THIS PROCEDURE
Connect a #6 AWG grounding wire (not included) from the ground connector (8) on the generator 
to a grounding rod (not included) that has been driven at least 24 inches deep into the earth. The 
grounding rod must be an earth-driven copper or brass rod (electrode) which can adequately 
ground the generator.