User Instructions
www.pulsar.pl            INTRE         
7 
4.  Configuration of the RS485-Ethernet interface. 
4.1 Introductory information. 
Ethernet  interface  parameters  can  be  configured  to  adjust  them  to  the  intended  operation  mode.  The 
configuration is done with „PowerConfig” program.  
  Download and install the „PowerConfig” program available on: 
 http://www.pulsar.pl/pliki/PowerConfig.exe 
The configuration of the RS485-Ethernet interface requires a minimum version of the connection, which is 
shown below. 
Fig. 4. The wiring diagram between the interface and the PC that enables performing the configuration. 
The RS485-ETHERNET interface is supplied in basic configuration (factory settings) which is not adapted 
for correct operation of the system. 
Since the communication with the interface uses a network cable, there is a need for proper configuration 
of the router in order to establish a connection with the interface. When using a switch, no configuration is required. 
When  using  a  router,  ask  the  administrator  about  the  current  configuration  of  the  router  or  restore  the  factory 
settings accordingly to the information included in the further part of this manual. 
4.2 STEP 1 - Restoring the factory settings. 
Router: 
To  restore  the  factory  settings  of  the  router,  check  the  manual  of  the  device  and  perform  appropriate 
actions according to the manufacturer's instructions. In most cases it is enough to find the reset button on the rear 
side of the enclosure and hold it for approximately 5 seconds. After releasing the reset button, wait about 1 minute 
for the correct initialization of the router.  
RS485-Ethernet interface: 
  In order to restore the factory settings of the interface, turn off the power, put the “RST” jumper on and turn 
on the power again. The factory settings will be restored after approximately 3 seconds.  
Remove the jumper before continuing. 