User Instructions
www.pulsar.pl EN54C-LS8
2
Installation.
1) The module should be installed in the fixed section of the enclosure.
2) Connect AUX1 and AUX2 outputs with 24 V module inputs using the supplied cables.
3) The parametric INPUT input should be connected to the actuator control device, e.g. the CSP control
panel.
4) If necessary, connect the PSU failure output.
When installing the fuse module in the power supply unit, power supply current consumption, used for the
calculation of standby time, should be considered.
Technical parameters.
Supply voltage
20 ÷ 30 V DC
Current consumption
20 ÷ 30mA @ Uin=20 ÷ 30 V DC
Output voltage
U
AUX
= U
IN
(according to supply voltage )
Output current
8 x 0,5 A
Number of power outputs
8 (OUT1 ÷ OUT8)
Overload protection
polymer fuses
Optical signaling of operation
8x LEDs - outputs condition OUT1÷OUT8 (green LEDs)
PSU - failure indication (red LED)
Control input
INPUT - parametric, 2x4,7 k
Operating conditions
2nd environmental class, -10°C ÷ 50°C
Dimensions (LxWxH)
150 x 52,5 x 27 [mm]
Net/gross weight
0,12kg / 0,14kg
Storage temperature
-20ºC...+60ºC
Additional equipment
Screws x 2
Pulsar sp.j.
Siedlec 150, 32-744 Łapczyca, Polska
Phone (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
WEEE Label
According to the European Union WEEE Directive, waste electrical and electronic equipment should be disposed of separately from normal
household waste.