Data Sheet
Features:
· supply voltage 20 ÷ 30 V DC
· eight outputs independently secured with melting fuses
· technical relay output of the PSU indicating fuse activation
· optical indication of failure
· dedicated to fire alarm power supplies of EN54C series
· warranty - 5 years from the production date
EN54C-LB8 v.1.0/I
EN54C LB8/0,5A/FTA fuse module
CODE:
NAME:
EN
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail: sales@pulsar.pl
Fuse modules EN54C
Pulsar
®
DESCRIPTION
.
The fuse module is designed for power distribution in the power supply units of EN54C series. It
contains two power inputs, IN1 and IN2, connecting to the power supply and eight independently secured
outputs AUX1÷AUX8. The IN1 input supplies power to the AUX1 and AUX4 outputs, while the IN2 input
supplies power to the AUX5 and AUX8 outputs. Each AUX output has short-circuit protection (SCP) in form of
F 0,5 A melting fuse (it is possible to install F1 A fuses - not included). Outputs condition is indicated by L1÷L8
LEDs. Fuse activation is indicated by: turning off the corresponding LED: L1 for AUX1, L2 for AUX2 etc.,
technical output relay type and PSU LED. PSU technical output can be used for remote control of the
parameters, e.g. external optical indication
Supply voltage
20 ÷ 30 V DC
Output voltage
U
AUX
= U
IN
(according to supply voltage )
Current consumption
20 ÷ 30mA @ Uin=20 ÷ 30 V DC
Number of power inputs
2 (IN1, IN2)
Number of power outputs
8 (AUX1 ÷ AUX8)
Protection:
- Short-circuit protection SCP
8 x F 0,5 A (it is possible to install F1 A fuses - not included)
Optical signaling of operation
L1 ÷ L8 - outputs condition AUX1÷AUX8 (green LEDs)
PSU - failure indication (red LED)
Fuses F1 ÷ F8
F0,5 A ÷ F1 A
PSU technical output
relay: 1 A@ 30 V DC/50 V AC
Operating conditions
2nd environmental class, -10°C ÷50°C
Dimensions (LxWxH)
150 x 52,5 x 27 [mm]
Net/gross weight
0,12kg / 0,14kg
Storage temperature
-20ºC...+60ºC
Additional equipment
Spacers x 2, glass fuses F0,5 A x 2
L
H
W