Data Sheet

20,0 V÷ 27,6 V DC – battery-assisted operation
Maximal resistance of the battery circuit
300m Ohm
Ripple voltage (max.)
30÷150m Vp-p max.
Current consumption by the PSU
during battery-assisted operation
52 ÷ 85mA
Coefficient of temperature compensation of the
battery voltage
-36mV/ ºC (-5 ºC ÷ 40 ºC)
The LoB low battery voltage indication
Ubat < 23 V, during battery mode
Overvoltage protection OVP
U>32 V±2 V, automatic recovery
Short-circuit protection SCP
F
AUX1
, F
AUX2
melting fuse (failure requires fuse replacement)
Overload protection OLP
105-150% of power supply, automatic recovery
Battery circuit protection SCP and reverse
polarity connection
F
BAT
melting fuse (failure requires fuse replacement)
Deep discharge battery protection UVP
U<20 V (± 2%) – disconnection of the batteries
TAMPER output indicating enclosure opening
Microswitch TAMPER
Technical outputs:
- EPS FLT; indicating AC power failure
- ALARM; indicating collective failure
- relay type: 1 A@ 30 V DC /50 V AC
- 10s time lag.
- relay type: 1 A@ 30 V DC /50 V AC
EXTi technical inputs
Closed input – no indication
Open input - alarm
Optical indication:
- LEDs on the PCB of the power supply unit (see section 3.3)
- LED panel
· 230 V mains power supply ON
· DC power at the AUX outputs
· failure indication
Additional equipment
(not included)
- fuse modules: EN54C-LB4, EN54C-LB8
- sequential modules: EN54C-LS4, EN54C-LS8
Operating conditions
2nd environmental class (EN 12101-10:2007), -5
o
C÷40
o
C
Enclosure:
Steel plate DC01, 1,0÷1,5mm, color: RAL 3001 (red)
Closing:
Key lock
Certificates, declarations, warranty
Certificate of constancy of performance CNBOP-PIB No 1438-CPR-0628,
certificate of approval CNBOP-PIB No 3501/2019,
CE, RoHS, 3 years from the production date
Notes:
The enclosure does not adjoin the mounting surface so that cables can be led.
Convection cooling.
PSU power Charging current Enclosure dimensions
EN54C-2A7
56,8 W
0,4 A 335 x 308 x 82 [mm]
EN54C-2A17
0,8 A 390 x 406 x 88 [mm]
EN54C-3A7
85,2 W
0,4 A 335 x 308 x 82 [mm]
EN54C-3A17
0,8 A 390 x 406 x 88 [mm]
EN54C-3A28
1,2 A 425 x 411 x 178 [mm]
EN54C-5A7
142 W
0,4 A 335 x 308 x 82 [mm]
EN54C-5A17
0,8 A 390 x 406 x 88 [mm]
EN54C-5A28
1,2 A 425 x 411 x 178 [mm]
EN54C-5A40
1,8 A 425 x 411 x 178 [mm]
EN54C-5A65
2,6 A 416 x 618 x 180 [mm]
EN54C-10A17
284 W
0,8 A 390 x 406 x 88 [mm]
EN54C-10A28
1,2 A 425 x 411 x 178 [mm]
EN54C-10A40
1,8 A 425 x 411 x 178 [mm]
EN54C-10A65
2,6 A 416 x 618 x 180 [mm]