User Instructions
www.pulsar.pl   EN54C    RED POWER plus 
5 
2. Functional requirements of the PSU. 
The buffer power supplies for fire alarm systems has been designed in accordance with the following 
standards: 
- EN 54-4:2001+A1:2004+A2:2007 Fire detection and fire alarm systems. 
- EN 12101-10:2007+AC:2007 Smoke and heat control systems. 
Functional requirements 
Requirements 
according to 
standards 
Power supplies 
EN54C series 
Two independent power sources 
YES 
YES 
External Power Supply failure indication 
YES 
YES 
Two independent power supply outputs protected against short-circuit 
YES 
YES 
Temperature-compensated battery charging 
YES 
YES 
Measurement of the resistance of the battery circuit 
YES 
YES 
Low battery indication 
YES 
YES 
Recharging the battery to 80% of the rated capacity within 24 hours 
YES 
YES 
Deep discharge battery protection 
YES 
YES 
Short-circuit protection of battery terminals 
YES 
YES 
Battery fuse failure indication 
YES 
YES 
Charging circuit failure indication 
YES 
YES 
Short-circuit protection 
YES 
YES 
Overload protection 
YES 
YES 
Output of collective failure ALARM 
YES 
YES 
EPS technical output 
YES 
YES 
Low output voltage indication 
- 
YES 
High output voltage indication 
- 
YES 
Indication of power supply failure 
- 
YES 
Overvoltage protection 
- 
YES 
Input of an external failure indication EXTi 
- 
YES 
Tamper indicating enclosure opening 
- 
YES 