Data Sheet

Power supplies series
Power supplies for fire alarm systems and
smoke and heat control systems
EN54C-LCD v.1.0/I
.
CODE:
TYPE:
PL
EN54C-LCD series power supply unit
Power supplies for fire alarm systems 27,6 V DC
Pulsar
®
“This product is suitable for the systems designed
in compliance with the standards EN 54-4 and EN 12101-10”
Functional requirements
Requirements
according to
standards
Power supplies
EN54C series
Two independent power sources YES YES
EPS network failure indication YES YES
Two independent power supply outputs protected against short-circuit YES YES
Temperature-compensated battery charging YES YES
Measurement of the resistance of the battery circuit YES YES
Low battery indication YES YES
Recharging the battery to 80% of the rated capacity within 24 hours YES YES
Deep discharge battery protection YES YES
Short-circuit protection of battery terminals YES YES
Battery fuse failure indication YES YES
Charging circuit failure indication YES YES
Short-circuit protection YES YES
Overload protection YES YES
Output of collective failure ALARM YES YES
EPS technical output YES YES
Low output voltage indication
-
YES
High output voltage indication
-
YES
Indication of power supply failure
-
YES
Overvoltage protection
-
YES
Input of an external failure indication EXTi
-
YES
Remote battery test
-
YES
Optical indication – LCD panel
-
YES
Tamper indicating enclosure opening
-
YES
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, www.zasilacze.pl, e-mail: sales@pulsar.pl
RED POWER plus

Summary of content (8 pages)