Overvoltage protection OVP
U>32 V±2V, automatic recovery
Short-circuit protection SCP
F4 A
F5 A
F6,3 A
F10 A
F
AUX1
, F
AUX2
melting fuse (failure requires fuse replacement)
Overload protection OLP
105-150% of power supply, automatic recovery
Battery circuit protection SCP and reverse
polarity connection
F5 A
F6,3 A
F10 A
F12,5 A
FBAT melting fuse (failure requires fuse replacement)
Deep discharge battery protection UVP
U<20 V (± 2%) – disconnection of the batteries
Tamper indicating enclosure opening
Microswitch TAMPER
Technical outputs:
EPS FLT; indicating AC power failure
ALARM; indicating collective failure
relay type: 1 A@ 30 V DC /50 V AC
delay 10s/1m/10m/30m (+/-5%) configured from the LCD panel (factory settings 10s)
relay type: 1 A@ 30 V DC /50 V AC
Technical inputs:
EXTi; external failure input
TAMPER; input of the microswitch tamper
Closed input no indication
Open input - alarm
Closed input no indication
Open input - alarm
Optical indication:
LEDs on PCB of power supply unit (see section 3.3)
LCD panel
display of electrical parameters, e.g. voltage, current, resistance of circuit readings
failure indication
PSU settings adjusted from panel’s level
operation memory of PSU 100 days
failure history 2048 events
real-time clock, battery-backed
LCD battery
3 V, lithium, CR2032
Fuses: F
BAT
F
AUX1
F
AUX2
F 5 A/250 V
F 4 A/250 V
F 4 A/25 0V
F 6,3 A/250 V
F 5 A/250 V
F 5 A/250 V
F 10 A/250 V
F 6,3 A/250 V
F 6,3 A/250 V
F 12,5 A/250 V
F 10 A/250 V
F 10 A/250 V
Additional equipment
(not included)
Interface RS485-TTL „INTR-C”; RS485 communication
Interface RS485-Ethernet INTRE-C”; RS485-Ethernet communication
Interface INTE-C; Ethernet communication
Fuse modules: EN54C-LB4, EN54C-LB8
Sequential modules: EN54C-LS4, EN54C-LS8