Table 12. Electrical parameters.
EN54C-2A7LCD
EN54C-2A17LCD
EN54C-3A7LCD
EN54C-3A17LCD
EN54C-3A28LCD
EN54C-5A7LCD
EN54C-5A17LCD
EN54C-5A28LCD
EN54C-5A40LCD
EN54C-5A65LCD
EN54C-10A17LCD
EN54C-10A28LCD
EN54C-10A40LCD
EN54C-10A65LCD
Functional class EN 12101-10:2007
A
Mains supply
~230 V
Current consumption
0,58 A
0,9 A
1,38 A
1,62 A
Inrush current
40 A
40 A
50 A
60 A
Power frequency
50 Hz
PSU’s power
56,8 W
85,2 W
142 W
284 W
Efficiency
88%
89%
87%
88%
Output voltage at 20ºC
22 V 27,6 V DC buffer operation
20 V 27,6 V DC battery-assisted operation
Continuous output current Imax a
1,6 A
1,2 A
2,6 A
2,2 A
1,8 A
4,6 A
4,2 A
3,8 A
3,2 A
2,4 A
9,2 A
8,8 A
8,2 A
7,4 A
Instantaneous output current Imax b (5 min)
2 A
3 A
5 A
10 A
Recommended battery capacity
7 Ah
17 Ah
7 Ah
17 Ah
28 Ah
7 Ah
17 Ah
28 Ah
40 Ah
65 Ah
17 Ah
28 Ah
40 Ah
65 Ah
The maximum battery capacity
7,2 Ah
20 Ah
7,2 Ah
20 Ah
28 Ah
7,2 Ah
20 Ah
28 Ah
45 Ah
65 Ah
20 Ah
28 Ah
45 Ah
65 Ah
Battery charging current
0,4 A
0,8 A
0,4 A
0,8 A
1,2 A
0,4 A
0,8 A
1,2 A
1,8 A
2,6 A
0,8 A
1,2 A
1,8 A
2,6 A
Net/gross weight [kg]
3,7/3,9
5,0/5,3
3,7/3,9
5,0/5,3
7,1/7,8
3,8/4,0
5,1/5,5
7,2/7,9
7,2/7,9
12,4/13,3
5,6/6,0
7,7/8,4
7,7/8,4
12,9/13,7
Maximal resistance of the battery circuit
300 mΩ
Ripple voltage (max.)
50 mVp-p
50 mVp-p
150 mVp-p
30 mVp-p
Current consumption by the PSU
during battery-assisted operation
64 mA
64 mA
67 mA
97 mA
Coefficient of temperature compensation of
the battery voltage
-36 mV/ ºC (-5ºC÷40ºC)
The LoB low battery voltage indication
Ubat < 23 V, during battery mode