User Instructions

www.pulsar.pl EN54C-LCD RED POWER plus
25
7.4.5. List of failure codes and information messages.
PSU indicates operation status with appropriate code. Codes are divided into two groups, marked with
initial letters „F” or „I”.
Codes beginning with letter „F” indicate a failure. Codes that begin with letter „I” indicate correct operation
of PSU or repaired fault, involving, for example, fuse replacement: „I03 - BAT fuse replaced”.
Table 7. List of failure codes of power supply unit.
Failure
code
Information
Technical
output
activation
Additional information
Additional
information
F01
AC power fail!
EPS FLT
ALARM
No AC mains supply
Burnt main fuse F
MAIN
F02
AUX1 fuse!
ALARM
Blown FAUX1 fuse
F04
Output overload!
ALARM
PSU overload
see section 5.4
F05
Undercharged
battery!
ALARM
Worn out battery
Undercharged batteries
see section 6
F06
High AUX1 voltage!
ALARM
Output voltage over 29.2 V
F08
Charge circuit fail!
ALARM
Output voltage of PSU set too low, below 26 V
Battery charging circuit failure
F09
Low AUX1 voltage!
ALARM
Output voltage below 26V
F10
Low battery voltage!
ALARM
Battery voltage has dropped below 23 V (during
battery-assisted operation)
F11
Low battery volt.
off!
ALARM
Battery voltage has dropped below 20 V (during
battery-assisted operation)
see section 6.4
F12
External input EXT!
ALARM
Activation of input of collective failure EXTi
see section 5.2
F14
Temp. sensor
malfunction!
ALARM
Temperature sensor damaged
Temperature sensor disconnected
see section 6.7
F15
High battery
temperature!
ALARM
The ambient temperature of the PSU is too hot
Batteries overloaded
Batteries damaged
see section 6.7
F16
No battery!
ALARM
Batteries disconnected
see section 6.1
F17
Battery fail!
ALARM
Batteries depleted, voltage below 20 V
see section 6.1
F18
High resistance of
battery circuit!
ALARM
Worn out battery
Battery connection cables loose
see section 6.6
F21
PSU cover opened!
ALARM
PSU cover opened
see section 5.3
F22
AUX2 fuse!
ALARM
Blown FAUX2 fuse
F26
High AUX2 voltage!
ALARM
Output voltage over 29.2 V
F29
Low AUX2!
ALARM
Output voltage below 26 V
F51
F52
internal damage of
PSU
ALARM
Service codes
F60
No communication
ALARM
No communication with LCD panel
F61
F64
Control panel fail
ALARM
Service codes
F65
Access unlocked
Passwords unlocked
F69-F74
Default settings
ALARM
Service codes