Power supply unit for fire systems used in building industry. Declared performance: Fire safety. Certificate of constancy of performance: 1438-CPR-0628 Certificate of admittance: 3501/2019 Conformity: EN 54-4:2001+ A1:2004 + A2:2007 EN 12101-10:2007 + AC:2007 USER MANUAL EN Edition: 2 from 31.07.2020 Supersedes the edition: 1 from 21.02.2019 Power supplies EN54C-LCD series v.1.0 Power supplies for fire alarm systems and smoke and heat control systems.
www.pulsar.pl EN54C-LCD RED POWER plus GENERAL SAFETY RULES Before installation, read the instruction manual to avoid errors that can damage the device and give you an electric shock. Before installation, cut off the voltage in the 230 V power-supply circuit. To switch power off, use an external switch, in which the distance between the contacts of all poles in the disconnection state is not less than 3mm.
www.pulsar.pl EN54C-LCD RED POWER plus TABLE OF CONTENTS 1. PSU FEATURES..................................................................................................................................... 5 2. FUNCTIONAL REQUIREMENTS OF PSU. ...................................................................................... 6 3. TECHNICAL DESCRIPTION. ............................................................................................................ 7 3.1. GENERAL DESCRIPTION................
www.pulsar.pl 8.3.2. 8.3.3. 8.3.4. 8.3.5. 8.3.6. EN54C-LCD RED POWER plus Setting date. .............................................................................................................................................................. 37 Setting time. .............................................................................................................................................................. 38 Setting backlight mode. ...........................................................
www.pulsar.pl RED POWER plus EN54C-LCD 1. PSU features. Compliant with requirements of EN 54-4:2001+A1:2004+ A2:2007 EN 12101-10:2007+AC:2007 standards and pt. 12.2 of Regulation of Minister of Interior and Administration of Republic of Poland of 27.04.
www.pulsar.pl RED POWER plus EN54C-LCD 2. Functional requirements of PSU. The buffer power supplies for fire alarm systems has been designed in accordance with the following standards: - EN 54-4:2001+A1:2004+A2:2007 Fire detection and fire alarm systems. - EN 12101-10:2007+AC:2007 Smoke and heat control systems. - pt. 12.2 of Regulation of Minister of Interior and Administration of Republic of Poland of 27.04.
www.pulsar.pl EN54C-LCD RED POWER plus 3. Technical description. 3.1. General description. The buffer power supplies has been designed for an uninterrupted supply of fire alarm systems, smoke and heat control systems, fire protection equipment and fire automatics requiring stabilized voltage of 24 V DC (±15%).
www.pulsar.pl 3.2. EN54C-LCD RED POWER plus Block diagram. The power supplies has been manufactured based on a high-efficiency system of AC/DC converter. Applied microprocessor circuit is responsible for the full diagnostics of the PSU parameters and batteries. The figure below shows a flowchart of the power supply, along with selected functional blocks which are essential for the proper functioning of the unit. Fig. 1. PSU block diagram. 3.3. Description of components and power supply terminals.
www.pulsar.pl EN54C-LCD Fuses: FBAT – fuse in the battery circuit, FAUX1 – fuse in the AUX1 output circuit, FAUX2 – fuse in the AUX2 output circuit, The fuse values are given in table 12 – "Electrical parameters".
www.pulsar.pl EN54C-LCD Table 2. Elements of PSU (Fig. 3). Component No. Description PSU (tab. 1, Fig. 2) Battery temperature sensor Battery connectors; positive: +BAT = red, negative: - BAT = black Place to install fuse module: INTE-C, INTR-C, INTRE-C A place for installation of additional modules TAMPER; microswitch (contacts) of antisabotage protection (NC) Fitting battery Embossing for cable gland Embossings for concealed wires Lock Fig. 3.
www.pulsar.pl EN54C-LCD RED POWER plus 4. Installation. 4.1. Requirements. The PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required for a given country) for ~230 V AC in and low-voltage installations. As the power supply is designed for a continuous operation and is not equipped with a powerswitch, therefore, an appropriate overload protection in the power supply circuit should be provided.
www.pulsar.pl EN54C-LCD 4.2. RED POWER plus Installation procedure. CAUTION! Before installation, cut off the voltage in the 230 V power-supply circuit. To switch power off, use an external switch, in which the distance between the contacts of all poles in the disconnection state is not less than 3mm. It is required to install an installation switch with a nominal current of 6 A in the power supply circuits outside the power supply unit. 1.
www.pulsar.pl 4.3. RED POWER plus EN54C-LCD Procedure for checking power supply at place of installation. 1 Check the indication displayed on the front panel of the power supply unit: a) The 230 V AC LED voltage. should remain lit to indicate the presence of the mains supply b) The LEDs AUX 1 and AUX 2 should remain lit to indicate presence of supply voltage. 2 Check the output voltage after 230 V power failure. a) Simulate the lack of 230 V mains voltage by disconnecting the main circuit breaker.
www.pulsar.pl EN54C-LCD RED POWER plus 5. Functions 5.1. Technical outputs. The power supply is fitted with relay indication outputs changing state upon the occurrence of a specific event. Fig. 6. Electrical diagram of relay outputs. EPS – output indicating 230 V power loss. The output indicates 230 V power loss. Under normal status – with the 230 V supply on, the output is closed. In case of power failure, the PSU will switch the output into the open position after a time 10s. (factory settings).
www.pulsar.pl EN54C-LCD RED POWER plus CAUTION! In Figure set of contacts shows a potential-free status of relay, which corresponds to power supply failure. 5.2. Input of collective failure: EXTi. The EXTi (external input) technical input indicating collective failure is intended for additional, external devices that generate the failure signal. Disconnection of the EXTi terminals will cause a failure of the PSU and generate a failure signal at the ALARM output.
www.pulsar.pl 5.3. EN54C-LCD RED POWER plus Indication of the enclosure opening – TAMPER. The PSU is fitted with the microswitch tamper indicating enclosure opening. The tamper cable is not connected to the terminal in the factory settings. In order to activate tamper, remove the jumper from tamper terminal and plug in the tamper cable. Each opening the enclosure will generate a failure signal at the ALARM technical output. Fig. 11. TAMPER technical output. 5.4. PSU overload.
www.pulsar.pl EN54C-LCD RED POWER plus 5.6.2. Cooperation with electric actuators – EN54C-LS4 and EN54C-LS8 sequential modules. The sequential modules are designed for use with electric actuators without return spring (EN54C-LS4) and with electric actuators with return spring (EN54C-LS8) used for fire dampers and smoke vents. These devices are used in fire alarm systems and smoke and heat control systems.
www.pulsar.pl EN54C-LCD RED POWER plus 6. Reserve power supply circuit. The PSU is fitted with intelligent circuits: battery charging circuit with the function of the accelerated charging and battery control, which main task is to monitor the condition of the batteries and the connections in the circuit. If the controller detects a power failure in the battery circuit, appropriate indication and change of the ALARM technical output. 6.1. Battery detection.
www.pulsar.pl EN54C-LCD RED POWER plus Fig. 13. Mounting of the temperature sensor. The PSU has a separate space in the internal memory, used for recording of the registered battery temperature. The recording cycle is performed in 6-hour intervals, enabling temperature registration for a period of 5 years. With such an extended registration period, the user is able to control the temperature fluctuation range and to determine its impact on the life of the batteries.
www.pulsar.pl RED POWER plus EN54C-LCD 7. LCD display – preview Table 3. Factory settings of PSU. Indication time of EPS network loss Acoustic indication Transmission Highlighting Blinking light indicating failure Passwords: – user’s – installer’s 7.1. 10s 1 115.2k 8E1 Constant – 50% ON section 8.2.2 section 8.2.3 section 8.2.4 section 8.3.4 section 8.3.6 section 8.1 1111 1234 Control panel.
www.pulsar.pl 7.2. RED POWER plus EN54C-LCD First run of PSU – language selection screen. During first run of PSU, language selection screen will be displayed. Use „<” or „>” buttons to select available languages. Fig. 15. Language selection screen. After selecting appropriate language, confirm by pressing „SET" button. Main screen will be displayed.. If language selection is not done, language selection screen will be displayed on next startup.
www.pulsar.pl 7.4. EN54C-LCD RED POWER plus Information displayed on LCD panel. 7.4.1. Preview menu. Pressing „ESC” button at bottom of display starts preview menu, allowing to choose one of four available PSU screens.. Use „<” or „>” buttons to choose a proper screen and press „SET” button to confirm. – current parameters of PSU (see section 7.4.2) – current failures of PSU (see section 7.4.3) – event log (see section 7.4.5) 7.4.2.
www.pulsar.pl RED POWER plus EN54C-LCD Table 6. Description of screen symbols - current parameters of PSU. Screen field Additional information Description – ~230 V power ON (highlighted = present mains supply 230 V) – indication power at AUX1 output (highlighted = present voltage at AUX1 output) – indication power at AUX2 output (highlighted = present voltage at AUX2 output) see section 8.2.2 – indicates battery failure (highlighted = battery failure) sections: 7.4.5 5.1 sections: 7.4.5 5.
www.pulsar.pl EN54C-LCD RED POWER plus Fig. 19. LCD screen – current failures of PSU. Screen displays codes and descriptions of failures. Display order of failures is arranged by priority of importance. First failures in display order are of highest priority. 7.4.4. LCD screen – history of parameters The user is able to check the malfunctions formerly signalled by the PSU. History of events screen enables overviewing events recorded by internal diagnostic system.
www.pulsar.pl RED POWER plus EN54C-LCD 7.4.5. List of failure codes and information messages. PSU indicates operation status with appropriate code. Codes are divided into two groups, marked with initial letters „F” or „I”. Codes beginning with letter „F” indicate a failure. Codes that begin with letter „I” indicate correct operation of PSU or repaired fault, involving, for example, fuse replacement: „I03 - BAT fuse replaced”. Table 7. List of failure codes of power supply unit.
www.pulsar.pl EN54C-LCD Table 8. List of failure codes and information messages. Message Description code I00 Power supply start-up I01 AC power back I02 AUX fuse replaced I04 Battery connected I05 Battery OK I06 Battery temp.
www.pulsar.pl RED POWER plus EN54C-LCD 8. LCD display – PSU settings. PSU has a configuration menu, allowing to configure PSU settings by changing or activating certain parameters. To enter setting mode, press „SET” button from main screen’s level. Fig. 22. PSU settings screen. 8.1. Password. PSU supports two levels of access to configuration, which limit possibility of changing PSU’s settings from LCD panel. Both levels are protected by a separate password.
www.pulsar.pl EN54C-LCD RED POWER plus – confirm by pressing „SET” button – use „<” or „>” buttons to enter first digit – confirm by pressing „SET” button – use „<” or „>” buttons to enter second digit – confirm by pressing „SET” button – use „<” or „>” buttons to enter third digit – confirm by pressing „SET” button – use „<” or „>” buttons to enter fourth digit – confirm by pressing „SET” button If entered password is wrong, following message will be displayed: Fig. 23.
www.pulsar.pl EN54C-LCD RED POWER plus 8.1.4. Resetting passwords. If the passwords are lost for any reason, a procedure may be performed to enable the reassignment of the factory default passwords. In order to perform this procedure, one should access the interior of the PSU casing. Locate the JP jumper in the rear part of the PCB of the LCD; it is used in the password unlocking procedure. Fig. 24. Location of the JP jumper used in the password unlocking procedure. Password unlocking procedure.
www.pulsar.pl EN54C-LCD RED POWER plus When on, keyboard will be locked automatically if no buttons are pressed within 5 minutes. After this time, pressing any button on control panel will display a window with keyboard password request. Enter password using „<” or „>” buttons as explained above. Fig. 25. Keyboard password request.
www.pulsar.pl EN54C-LCD 8.2. RED POWER plus PSU. „PSU” menu is only available after entering the correct service password. Selecting „PSU” in settings menu will display another menu, allowing full configuration of PSU: battery test performance, setting delay time for EPS output and setting communication parameters. After entering right settings, they are stored in internal non-volatile memory, which protects PSU against data loss in case of a failure or power failure. Fig. 26. „PSU” screen. Table 10.
www.pulsar.pl EN54C-LCD RED POWER plus – during the test, the WAIT message appears on the screen The PSU has a software protection against too frequent testing of batteries, which could cause them to undercharge. The protection consists in blocking the option of performance of the test for 60 s since it has last been enabled. In such situation, the „WAIT” message appears on the LCD in the Settings -> PSU -> Battery Test menu. Fig. 27. Temporary battery test blockade.
www.pulsar.pl EN54C-LCD RED POWER plus 8.2.2. Setting delay time for EPS output indicating 230 V AC power loss. PSU features adjustable delay for 230 V AC power loss indication. Delay time can be selected from four available ranges: 10s (factory settings) 1min 10min 30min 230 V power loss is indicated by activation of „EPS FLT” and „ALARM” technical output.
www.pulsar.pl EN54C-LCD RED POWER plus 8.2.3. Setting communication address – refers to cooperation with the interface. All power supplies are factory-set to address 1. Communication address allows to identify power supply units in same communication network RS485.
www.pulsar.pl EN54C-LCD RED POWER plus 8.2.4. Setting transmission parameters – refers to cooperation with the interface.
www.pulsar.pl 8.3. EN54C-LCD RED POWER plus Control panel. Menu is only available after entering correct user’s or service password. „Control panel” menu enables configuration of settings directly related to user interface. It is possible to set display language, date, time, intensity of backlight and blinking light indicating failure. Setting correct date and time is important for keeping chronology of events stored in internal memory.
www.pulsar.pl EN54C-LCD RED POWER plus 8.3.1. Setting display language. One of functions of control panel menu is possibility to select language. Display language can be set according to personal preference.
www.pulsar.pl EN54C-LCD RED POWER plus – use „<” or „>” buttons to set current month – press „SET” button, prompt will appear next to day position – use „<” or „>” buttons to set current day – confirm by pressing „SET” button 8.3.3. Setting time. „Time” menu in „Control panel” menu enables setting correct time, according to which error messages and operation history will be saved.
www.pulsar.pl EN54C-LCD RED POWER plus 8.3.4. Setting backlight mode. „Backlight” menu dims display if no buttons are pressed within 5 min and sets intensity of backlight.
www.pulsar.pl EN54C-LCD 8.3.5. Contrast setting. „Contrast” menu in „Control panel” enables setting contrast of display text.
www.pulsar.pl EN54C-LCD RED POWER plus 8.3.6. Blinking light indicating failure "Blinking light indicating failure” menu enables setting backlight mode during failure indication. When on, blinking light will indicate a failure.
www.pulsar.pl EN54C-LCD RED POWER plus 9. Remote monitoring (options) PSU has been adjusted to operate in a system that requires a remote control of parameters in a monitoring centre. Implementation of this function is possible upon installation of an additional communication interface. Data are transmitted using the modbus protocol, and their exchange may be effected through a RS485 bus or through the Ethernet.
www.pulsar.pl EN54C-LCD RED POWER plus Fig. 32.
www.pulsar.pl 9.3. EN54C-LCD RED POWER plus „PowerSecurity” web application The PowerSecurity web application has been embedded in the INTE-C and INTRE-C communication interfaces. The programme is a website uploaded from an embedded WWW server which is loaded upon entering the IP address in the web browser window. Upon loading the PowerSecurity application, access is gained to the preview of the status of the PSU connected with the INTE-C interface (see Section 9.
www.pulsar.pl EN54C-LCD RED POWER plus The web application also has a graphic tab „Graphs” from which the PSU history of operation may be downloaded and viewed in the graphic form, as a graph. A read graph may be saved in a file on a disc. Fig. 34. View of the history of operation of PSU. Another tab enabling checking of the PSU history is the tab of events. The read history is displayed as a table, following a chronological order.
www.pulsar.pl EN54C-LCD RED POWER plus The PowerSecurity programme provides functionality in the form of a remote battery test and the function of remote alerting via automatically sent email notifications. The notifications contain information on the current error codes, with the exact malfunction occurrence time. The email notifications are sent to 2 recipients.
www.pulsar.pl RED POWER plus EN54C 10. Technical parameters. Electrical parameters (Table 12). Mechanical parameters (Table 13). Safety of use (Table 14). Operation parameters (Table 15). Recommended types and sections of installation cables (Table 16).
www.pulsar.
www.pulsar.pl RED POWER plus EN54C Table 13. Mechanical parameters. Battery space: Enclosure dimensions Mounting (WxH) Fitting battery (WxHxD) (max.
www.pulsar.pl RED POWER plus EN54C Table 15. Operation parameters. Environmental class EN 12101-10:2007 Operating temperature Storing temperature Relative humidity Sinusoidal vibrations during operation: 10÷50 Hz 50÷150 Hz Surges during operation Direct insolation Vibrations and surges during transport 1 -5oC÷40oC -25ºC...+60ºC 20%...90%, no condensation 0,1 G 0,5 G 0,5 J unacceptable According to the PN-83/T-42106 standard Table 16. Recommended types and sections of installation cables.
www.pulsar.pl EN54C RED POWER plus 11. Technical inspections and maintenance. Technical inspections and maintenance can be performed after disconnecting the power supply from the power network. The PSU does not require any specific maintenance, however, its interior should be cleaned with compressed air if it is used in dusty conditions. In case of fuse replacement, use only compatible replacement parts. Technical inspections should be carried out not less frequently than once per year.