Operating instructions

www.pulsar.pl EN54-5A40LCD RED POWER
8
4.3. Description of components and power supply terminals.
Table 1. Components of the Power supply PCB (Fig. 2).
Compon
ent No.
Description
[1]
PANEL optical indication connector
[2]
BUZZER acoustic indication (section 7.2.2)
[3]
V
EXT
jumper
polarization of the EXTi circuit (section 6.6)
[4]
F
BAT
fuse in the battery circuit, F10A / 250V
[5]
F
AUX1
fuse in the AUX1 output circuit, F6,3A / 250V
[6]
F
AUX2
fuse in the AUX2 output circuit, F6,3A / 250V
[7]
SERIAL communication port
[8]
Z2 jumper
temporary lock of the battery test (section 8.5)
The EXTo relay switch lock from the PowerSecurity application-level (section 7.2.3)
[9]
OVP overvoltage protection optical indication (section 6.9)
[10]
LEDs optical indication:
AC AC power
AUX1 AUX1 output voltage
AUX2 AUX2 output voltage
OVL PSU overload
APS battery failure
PSU PSU failure
ALARM collective failure
EXTi EXTi input status
EXTo EXTo relay output status
LB battery charging
[11]
Terminals:
~AC~ AC power input
EPS FLT technical output of AC power failure indication
open = AC power failure
close = AC power - O.K.
PSU FLT technical output of PSU failure indication
open = failure
close = PSU operation - O.K.
APS FLT technical output of battery failure
open = battery failure
close = battery status - O.K.
ALARM technical output of collective failure of the PSU -
relay type
CAUTION! In Fig.2 the set of contacts shows a
potential-free status of the relay, which corresponds to
power supply failure.
EXTo controlled relay output
EXTi input of collective failure
+BAT- terminals for connecting the battery
+AUX1- AUX1 power output
(+AUX1= +U, -AUX=GND)
+AUX2- AUX2 power output
(+AUX2= +U, -AUX=GND)
[12}
TAMPER antisabotage protection microswitch connector (section 6.7)
[13]
Connector for connecting the EMC filter
Fig. 2. The view of the PSU’s PCB.