Operating instructions
www.pulsar.pl EN54-5A40LCD RED POWER
45
W
H
D
real time clock with battery backup
Acoustic indication:
- piezoelectric indicator ~75dB /0,3m, switched from the LCD
panel
LCD screen battery
3V lithium battery, CR2032
Fuses:
- F
MAINS
- F
BAT
- F
AUX1
- F
AUX2
T 6,3A / 250V
F 10A / 250V
F 6,3A / 250V
F 6,3A / 250V
Additional equipment
(not included)
- USB-TTL „INTU” interface; USB-TTL communication
- RS485 „INTR” interface; RS485 communication
- USB-RS485 „INTUR” interface; USB-RS485 communication
- Ethernet „INTE” interface; Ethernet communication
- WiFi “INTW” interface; WiFi wireless communication
- RS485-Ethernet “INTRE” interface; RS485-Ethernet
communication
- RS485-WiFi “INTRW” interface; RS485-WiFi wireless
communication
Table 16. Mechanical parameters.
Enclosure dimensions
W=420 H=420 D+D
1
=182 + 8 [+/- 2mm]
W
1
=425 H
1
=425 [+/- 2mm]
Mounting
380 x 345 x Φ 6 x4 pieces (WxH)
Recommended battery model
- 2 x EP 42-12 or
- 2 x GP12400
Fitting battery
2x40Ah/12V (SLA) max.
400 x 180 x 175mm (WxHxD) max
Net/gross weight
11,1/12,7 kg
Enclosure
Steel plate DC01 1,2mm, color: RAL 3001 (red)
Closing
Key lock
Terminals
Mains supply: Ф0,51÷2 (AWG 24-12)
Outputs: Ф0,51÷2 (AWG 24-12)
Battery outputs BAT: Ф6 (M6-0-2,5)
Cable glands
PG9 – cable diameter Ф4÷8mm
PG11 – cable diameter Ф5÷10mm
Notes
The enclosure does not adjoin the mounting surface so that cables can be led.
Convection cooling.