Operating instructions

www.pulsar.pl          EN54-3A28              RED POWER 
4
1. PSU features: 
• In accordance with standards: EN 54-4, 
 EN12101-10 
• 27,6V DC/ 3A uninterruptible power supply 
• battery housing for two 28Ah/12V batteries 
• independently protected outputs AUX1 and AUX2 
• high efficiency 84% 
• low level of voltage ripple 
• microprocessor-based automation system 
• intelligent PSU overload protection 
• measurement of the resistance of the battery circuit 
• automatic temperature-compensated charging 
• battery test 
• two-stage battery charging process 
• accelerated battery charging 
• monitoring of the continuity of the battery circuit 
• monitoring of the battery voltage 
• monitoring of the battery fuse 
• monitoring of charging and maintenance of the 
batteries 
• deep discharge battery protection (UVP) 
• battery overcharge protection 
• battery output protection against short-circuit and 
reverse connection 
• monitoring of the load current 
• output voltage control 
• fuse monitoring of AUX1and AUX2 outputs 
• 230V AC mains supply voltage measurement 
• „SERIAL” communication port with implemented 
MODBUS RTU protocol 
• free program "PowerSecurity" to monitor the 
performance of the PSU 
• remote monitoring (options: WiFi, Ethernet, RS485, 
USB) 
• remote battery test (additional modules required) 
• cooperation with optional EN54-LB4 or EN54-LB8 
fuse modules 
• optical indication of PSU overload OVL 
• acoustic indication of failure 
• adjustable delay for 230V AC power loss indication 
• output of collective failure ALARM 
• input of collective failure EXTi 
•  controlled relay output EXTo 
•  technical inputs/outputs with galvanic isolation 
•  EPS technical output indicating 230V AC power loss 
•  PSU technical output indicating PSU failure 
•  APS technical output indicating battery failure 
•  internal memory of PSU operating status 
• optical indication – LED panel 
•  output current readings 
•  output voltage readings: AUX1, AUX2 
•  resistance of the battery circuit 
• 
230V AC
 mains voltage readings 
•  failure codes with history 
• protections: 
•  SCP short-circuit protection 
•  OLP overload protection 
•  OHP overheat protection 
•  OVP overvoltage protection 
•  Surge protection 
•  Antisabotage protection - Tamper 
• closing the enclosure - lock 
• convection cooling 
• warranty - 5 years from the production date 