I.  Within 5 minutes the PSU will start signaling a failure in the battery circuit. 
II.  The ALARM LED will start blinking. 
III.  The APS and ALARM technical outputs will change status into opposite. 
IV.  Acoustic indication will be activated. 
b)  Reconnect the wires in the battery circuit.  
c)  The power supply should return to normal operation, indicating the initial status, within 5 
minutes after the battery test is completed. 
3. PSU operation indication. 
3.1 Optical indication.  
The PSU is fitted with three LED lights at the front panel 
AC voltage 
  ON - PSU supplied with 230V AC voltage 
  OFF - no 230V AC supply 
24V DC output voltage 
  ON - 24V DC voltage at the MIC output of the power supply 
  OFF - no 24V DC voltage at the MIC output of the power supply 
 FAILURE  
Collective failure  
  blinking - failure 
  OFF – normal operation 
3.2 Technical outputs. 
The power supply is fitted with relay indication outputs changing state upon the occurrence of a specific event: 
  EPS FLT – output of 230V AC power failure indication. 
Output  indicating  230V  AC  power  failure.  Under normal  status  –  with  the  230V  AC  supply on  - the 
output is closed (open *); in the case of power failure the output is switched to an open state (shorted *) 
after 10 seconds. 
  APS FLT– output of battery failure indication. 
Output indicating failure in the battery circuit. Under normal status – with the 230V AC supply on - the 
output is closed (open *); in the case of failure the output is switched to an open state (shorted *). Failure 
can be triggered by the following events: 
    - Faulty battery 
    - Undercharged battery 
    - Disconnected battery 
    - High resistance of the battery circuit 
    - Battery voltage below 11,5V during battery-assisted operation 
- Battery fuse failure 
- No continuity in the battery circuit 
  PSU FLT – output of power supply failure indication  
Output indicating PSU failure. Under normal status – with the 230V AC supply on - the output is closed 
(open *); in the case of failure the output is switched to an open state (shorted *). Failure can be triggered 
by the following events: 
    - Battery voltage below 13V 
    - Battery voltage higher than 14,6V 
    - Failure of the battery charging circuit 
- F
AUX 
fuse failure 
- Too high battery temperature 
- Temperature sensor failure 
- Internal damage of the power supply 
  ALARM – technical output of collective failure indication. 
Output indicating collective failure. Under normal status – with the 230V AC supply on - the output is 
closed (open *); in the case of failure at any EPS, APS, or PSU output, the output is switched to an open 
state (shorted *).  
* Depending on the position of the jumper for configuring the relay contacts, see Table 1, item 8 