User Instructions
www.pulsar.pl                  
10 
4. Maintenance and operation. 
4.1. Overload or short circuit of the power supply output (SCP activation) 
In the case of short circuit or overload of the power supply, the F
AUX
 fuse becomes permanently damaged. 
Restoration of the voltage at the output requires fuse replacement 
4.2. Protection against reverse battery connection. 
The power supply unit is protected against reverse battery connection. In the case of incorrect connection 
the FBAT fuse becomes damaged. The return to normal operation is possible  only after replacing the  fuse and 
correct connection of the batteries. 
4.3. Deep discharge battery protection (UVP). 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the  battery-assisted 
operation, reducing voltage below 10V±1V at the battery terminals will disconnect the battery within 15 seconds. 
Re-connecting the battery to the power supply occurs automatically once the 230V mains voltage is restored. 
4.4. Battery test 
The PSU performs the battery test every 5 minutes. During the test the power supply controller measures 
the electrical parameters in accordance with the implemented measurement procedure.  
A negative result occurs when the continuity of the battery circuit is interrupted, the resistance in the battery 
circuit is above 300 mΩ, or when the terminal voltage drops below 12V. 
The  battery test  is  automatically locked when  the  power  supply is  in the  mode in  which performing the 
battery test  is not  possible.  Such a  state occurs, e.g.  during battery-assisted  operation or  in  the case  of power 
supply overload. 
4.5. The measurement of the resistance of the battery circuit 
The power supply unit is fitted with a function that checks the resistance in the battery circuit. During the 
measurement, the power supply controller takes into account the key parameters in the circuit and in the case of 
exceeding the limit value of 300m Ohm it indicates failure.  
A failure may indicate significant battery consumption or loosening of the connection cables. 
4.6. Measurement of the battery temperature 
The  power  supply  unit  is  fitted  with  a  temperature  sensor  to  monitor  the  temperature  parameters  of  the 
installed battery. 
The measurement of the battery temperature and the charging voltage compensation extend the battery life.  
4.7. Maintenance. 
Technical inspections and maintenance can be performed after disconnecting the power supply from the 
power network 
In the case of fuse replacement, use a replacement of the same parameters 
Re-tighten all screw connections after 4 weeks from installation of the power supply. 2 [9.10]. 