DSOS24V v.1.0 FIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V EN* Edition: 3 from 05.02.2020 Supercedes edition: 2 from 30.08.
www.pulsar.pl PSU features. Compliant with the requirements of the EN 54-4:1997+AC:1999+A1:2002+A2:2006 and EN 12101-10:2005+AC:2007standards and pt. 12.2 of the Regulation of the Minister of Interior and Administration of the Republic of Poland of 20.06.2007 Power supply for the call station of the DSO system, e.g.
www.pulsar.pl TABLE OF CONTENTS: 1. Technical description. 1.1 General description. 1.2 Block diagram. 1.3 Description of components and power supply connectors. 1.4 Technical parameters 2. Installation. 2.1 Requirements 2.2 Installation procedure. 2.3 The procedure for checking the power supply 3. PSU operation indication. 3.1 Optical indication of operation. 3.2 Technical outputs. 4. Maintenance and operation. 4.1 Overload or short circuit of the power supply output (SCP activation) 4.
www.pulsar.pl 1.3 Description of components and power supply connectors. Table 1. Components of the PCB of the power supply (see Fig. 2). Componen Description t No.
www.pulsar.pl Table 2. Components of the power supply (see Fig. 3). Component Description No. Mounting shelf with dimensions of 540 x 190 [mm] for the call station PVA-15CST and two PVA-20CSE extensions by BOSCH LED lights - optical indication: AC – AC voltage DC – 24V DC output voltage FAILURE – collective failure Battery space for a 7Ah/12V battery Battery connectors; positive: +BAT = red, negative: - BAT = black PE-N-L power connector 230V AC, FMAIN=T3,15A / 250V Fig.3.
www.pulsar.pl 1.4 Technical parameters: - Electrical parameters (Table 2) - Mechanical parameters Table 3) - Safety of Use (Table 4) - Operation parameters (Table 5) Table 2. Mechanical parameters.
www.pulsar.pl Table 4. Safety of Use. Protection class PN-EN 60950-1:2007 Protection grade PN-EN 60529:2003 Insulation electrical strength: - between the input (network) circuit and the output circuits of the PSU (I/P-O/P) - between the input circuit and PE protection circuit (I/P-FG) - between the output circuit and PE protection circuit (O/P-FG) Insulation resistance: - between input, output, and protective circuit Table 5. Operation parameters.
www.pulsar.pl 3. Connect the RJ45-RJ45 cable from the call station of the "CST BUS" to the "MIC" jack on the power supply board. Fig. 4. Connecting the call station to the power supply. 4. Mount the mounting brackets to the call station paying attention to their correct position in relation to the right "P" and left "L" sides. 5. Connect the transmission cable (from the DSO „CST-BUS” control panel) to the "IN" connector on the power supply board (mark 1..8). 6.
www.pulsar.pl I. Within 5 minutes the PSU will start signaling a failure in the battery circuit. II. The ALARM LED will start blinking. III. The APS and ALARM technical outputs will change status into opposite. IV. Acoustic indication will be activated. b) Reconnect the wires in the battery circuit. c) The power supply should return to normal operation, indicating the initial status, within 5 minutes after the battery test is completed. 3. PSU operation indication. 3.1 Optical indication.
www.pulsar.pl 4. Maintenance and operation. 4.1. Overload or short circuit of the power supply output (SCP activation) In the case of short circuit or overload of the power supply, the FAUX fuse becomes permanently damaged. Restoration of the voltage at the output requires fuse replacement 4.2. Protection against reverse battery connection. The power supply unit is protected against reverse battery connection. In the case of incorrect connection the FBAT fuse becomes damaged.