Data Sheet
wyjście TAMPER : przewody 30cm
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail: sales@pulsar.pl
DSOS24V series power supply unit
Fireman's microphone power supply for the voice alarm systems 24V
Pulsar
®
SPECIFICATIONS
Functional class PN-EN 12101-10:2007
1
Supply voltage
176 ÷ 264V AC
Current consumption
0,15A @230V AC
Power supply frequency
50Hz
PSU power
10W
Rated voltage
24V DC
Output current
200mA
The maximum resistance of the battery
circuit
300m Ohm
Ripple voltage
45mV p-p max.
Current consumption by PSU systems
during battery operation
I = 115mA
Battery charging current
0,4A
The coefficient of temperature
compensation of the battery voltage
-20mV/ ºC (-5ºC ÷ 40ºC)
Low battery voltage indication
Ubat < 11,5V, during battery operation
Short-circuit protection SCP and overload
protection OLP
F500mA melting fuse at the 24V DC output (requires fuse
replacement)
Battery circuit protection SCP and reverse
polarity connection
T2A- F
BAT
melting fuse (failure requires fuse replacement)
Deep discharge battery protection (UVP)
U<10V (± 1V) – disconnecting (+BAT) the battery
Technical outputs:
- EPS FLT; output indicating AC
power failure
- APS FLT; output indicating battery failure
- PSU FLT; output indicating PSU failure
- ALARM; output indicating collective failure
- relay type: 0.5A@ 30VDC/50VAC
Optical indication.
- AC; LED indicating AC power status
- DC; LED indicating 24V DC power status at
the PSU output
- FAILURE; LED indicating failure
- green, normal status: permanently illuminated,
failure: not lit
- green, normal status: permanently illuminated,
failure: not lit
- yellow, normal status: not lit,
failure: permanently illuminated
Fuses:
- F
AUX
- F
BAT
- F
MAIN
F500mA / 250V
T2A / 250V
T3,15A / 250V
Operating conditions:
1 environmental class (PN-EN12101-10 :2007), -5ºC ÷ 40ºC
Enclosure:
DC01 steel plate 1 mm, color red (RAL 3001)
Enclosure dimensions:
550 x 380 x 200 (WxHxD) [mm] (+/- 2)
Fitting battery:
7Ah/12V (SLA)
Net/gross weight:
9,8/10,5 kg
Certificates
Deklarations, warranty:
Certificate of constancy of performance CNBOP-PIB
No 1438-CPR-0504,
Certificate of approval CNBOP-PIB No 2830/2017,
CE, 3 year from the production date
Notes:
Convection cooling.