Data Sheet

Table Of Contents
DSOS24V v.1.0/III
Fireman's microphone power supply for the voice alarm systems 24V
CODE:
TYPE:
DESCRIPTION
The DSOS24V is designed for uninterruptible power supply of call stations (firefighter's microphone) used in
VAS (Voice Alarm Systems) requiring stabilized voltage of 24V DC (-5%/+5%).
In the case of mains power loss, the PSU immediately switches to battery power. The power supply unit
is housed in a metal enclosure (color red RAL 3001) with space for a 7Ah / 12V battery. The power supply unit
uses maintenance free, AGM or gel batteries (7Ah/12V).
wyjście TAMPER : przewody 30cm
Tel .+48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail: sales@pulsar.pl
DSOS24V series power supply unit
Fireman's microphone power supply for the voice alarm systems 24V
Pulsar
®
EN**
PSU features:
· Compliant with the requirements of the
EN 54-4:1997+AC:1999+A1:2002+A2:2006
and EN 12101-10:2005+AC:2007standards and pt. 12.2
of the Regulation of the Minister of Interior and
Administration of the Republic of Poland of 20.06.2007
· Power supply for the call station of the DSO system, e.g.
the PVA-15CST and two PVA-20CSE extensions by
BOSCH
· 24V DC Uninterruptible Power Supply
· Single battery power supply (7Ah /12V)
· Wide supply voltage range (176-264V AC)
· Low ripple voltage
· Microprocessor-based automation system
· Measurement of the resistance of the battery circuit
· Automatic temperature compensation of the battery
charging
· Battery test
· Two-phase battery charging
· The accelerated battery charging
· Battery electrical continuity control
· Battery voltage control
· Battery fuse status control
· Battery charge and maintenance control
· Deep discharge battery protection (UVP)
· Battery overload protection.
· Battery output protection against short-circuit
and reverse polarity connection
· Output voltage control
· Acoustic indication of failure
· Technical inputs/outputs with galvanic isolation
· Technical outputs - relay type.
· ALARM – technical output of collective failure
· EPS – technical output of 230V AC power
failure indication
· PSU – technical output of power supply failure
indication
· APS – technical output of battery failure indication
· LED Optical indication.
· Protection types:
· SCP short-circuit protection
· OLP overload protection
· Convection cooling.
· Warranty – 3 year from the production date
1438
17
Power supply unit for fire systems used in building industry.
Declared performance: Fire safety.
Certificate of constancy of performance: 1438-CPR-0504
Certificate of admittance: 2830/2017
Conformity: EN 54-4:1997+AC:1999+A1:2002+A2:2006
EN 12101-10:2005+AC:2007

Summary of content (2 pages)