User Instructions
www.pulsar.pl DINB27620
4
Overload protection OLP
150-200% of the PSU power, automatic return
Surge protection
varistor
Deep discharge battery protection UVP
U<20V (+/- 0,5V) – disconnection of the battery terminal
Optical indication of operation
YES – LEDs
F1 fuse
T 3,15A / 250V
F2 fuse
F 2A / 250V
Mechanical parameters (Table 3)
Dimensions
L=122, W=93, H=50 [+/- 2mm]
Mounting
TH35 DIN rail
Net/gross weight
0,37 kg/ 0,45 kg
Enclosure
ABS, RAL9003, white
Connectors
Φ0,51-2,05 (AWG 24-12)
Safety of use (Table 4)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output circuit
100 MΩ, 500V/DC
Operation parameters (Table 5)
Environmental class
II
Operating temperature
-10ºC...+40ºC
Storing temperature
-25ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation
unacceptable
Surges during operation
unacceptable
Direct insolation
unacceptable
Vibrations and surges during transport
compliant with the PN-83/T-42106
2. Installation.
2.1 Requirements.
The power supply unit should be mounted by a qualified installer, holding relevant permits and licenses
(applicable and required for a given country) for 230V/AC and low-voltage installations. The unit should be
mounted in confined spaces, in accordance with the 2nd environmental class, with normal relative humidity
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The power supply should
operate in a vertical position in order to provide free and convectional air flow through ventilating holes of the
enclosure
The power supply load balance should be done before installation. During normal operation, the total
current of the receivers should not exceed I=2A. The maximum battery charging current is 0,2A. The total
current of the receivers + battery is max. 2,2A.
The power supply is designed for a continuous operation and is not equipped with a power-
switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards and
The unit should be mounted in a metallic enclosure (telecommunication cabinet) fitted with TH35 DIN rail (35 mm
width); in order to meet the LVD and EMC requirements, the rules concerning power supply, building-in and
shielding should be followed accordingly.