User Instructions
4 
2.2. Installation procedure. 
1. Mount the enclosure (cabinet, etc.) and lead cables through cable glands. 
2. Mount the DC/DC converter with adhesive tape or mounting screws. 
3. Supply DC voltage to the + IN, -IN terminals with correct polarization. 
4. Switch on the DC voltage. 
5. Use the V
ADJ
 potentiometer to set the required output voltage. The factory setting: 12V. 
6. Switch off the DC voltage. 
7. Connect the receivers’ cables to the +AUX, -AUX connectors of the terminal block on the module’s board. 
8. Connect the device cables (alarm control panel, indicator, LED light, etc.) to the PSU technical output if necessary. 
9. Switch on the DC voltage (the red IN LED should be permanently illuminated, the AUX green LED should be permanently 
illuminated). 
10. Once the tests and operation control are performed, close the enclosure, cabinet, etc. 
3. Converter 's module operation indication. 
3.1. Technical output. 
The converter is equipped with three diodes indicating operation status: IN, AUX, and PSU. 
  IN- red LED: during normal status (DC power supply) it is lit continuously. No DC supply is indicated by switching off the IN LED. 
  AUX- green LED: indicates DC supply status at the module’s output. During normal status, it is lit continuously, in case of short 
circuit or overload the AUX led is off. 
  PSU- red LED:  indicates  module’s  overload.  During  normal  status,  it  is  off,  in  case  of short  circuit  or overload  the LED  lights 
continuously. 
3.2. Technical output. 
The converter is fitted with one technical output indicating failure of the DC / DC module. 
  PSU- OLP/SCP (overload/short-circuit) output: - OC type output indicating overload/short-circuit of the module’s output. 
During normal operation, the output is shorted to the AUX - (0V). In case of failure, the module disconnects the output and it is in the hi-
Z (high impedance) state during failure. 
4. Maintenance and operation. 
4.1. Converter overload. 
The AUX output is  protected  with  the  PTC  polymer  fuse.  If  the  load  current  exceeds  Imax  (110%  ÷  150%  @  25ºC  of  the 
converter capacity), the output voltage will be automatically disconnected, which will be  signaled by switching off the green AUX LED, 
switching on the red PSU LED and a change in the status of the technical output. Voltage restoration requires disconnecting the output 
load for approx. 1 min. 
5. Maintenance. 
 All maintenance procedures can be performed after disconnecting the converter from the power network. The converter does 
not require any specific maintenance; however, its interior should be cleaned with compressed air if used in dusty conditions. 
WEEE LABEL 
Waste electrical and electronic equipment must not be disposed of with normal household waste. 
According to the European Union WEEE Directive, waste electrical and electronic equipment should be 
disposed of separately from normal household waste. 
Pulsar sp. j. 
Siedlec 150, 32-744 Łapczyca, Poland 
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 
e-mail: biuro@pulsar.pl, sales@pulsar.pl 
http:// www.pulsar.pl, www.zasilacze.pl 