Table 6. Table of errors
State, failure
Optical
indication
Acoustic
indication
Technical
output
Causes, comments
The start of the test
Absence
2 short beeps
INACTIVE
- Start of the battery test
High resistance of the
BAT circuit
Blinks
1 beep every 10
seconds
ACTIVE
- Batteries worn out
- Loose connectors
Undercharged battery
Blinks
1 beep every 10
seconds
ACTIVE
- Undercharged battery
No battery
Blinks
1 beep every 10
seconds
ACTIVE
- Blown F
BAT
fuse
- No battery
Low battery voltage
(DC operation)
Lit
2 short beeps
every 10 seconds
ACTIVE
- The batteries voltage has
dropped below 23V during battery
(assisted operation)
Low battery voltage -
disconnection
(DC operation)
Absence
2 beeps every 10
seconds
(without repeat)
ACTIVE
- The batteries voltage has
dropped below 21V during battery
(assisted operation)
4. Maintenance and operation.
4.1. Automatic battery test
The battery controller performs a battery test every 5 minutes, temporarily stopping the charge process, while
measuring voltage at the battery terminals and the resistance of the battery circuit. The test can also be started manually
by pressing the "TEST" button on the front panel, but not more often than once every 1 minute. The activation or
deactivation of the test will be confirmed acoustically (see Table 6).
4.2. Short circuit of the controller output/reverse connection.
The BAT controller output is additionally protected against short circuit by a fuse (box); in the case of damage, it
should be replaced with a fuse of the same type. The fuse is located inside the unit.
4.3. Maintenance.
The battery controller does not require any specific maintenance; however, it should be cleaned with
compressed air if used in dusty conditions.
WEEE LABEL
Waste electrical and electronic equipment must not be disposed of with normal household waste.
According to the European Union WEEE Directive, waste electrical and electronic equipment
should be disposed of separately from normal household waste
.
The battery controller is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled
according to the applicable law.
Pulsar sp. j.
Siedlec 150, 32-744 Ɓapczyca, Polska
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl