Fig. 2. General view. 
1.4.  Technical parameters. 
- Electrical parameters (Table 2) 
- Mechanical parameters (Table 3) 
- Operation safety (Table 4) 
-
Operation parameters (Table 5) 
 Electrical parameters (Table 2). 
Fitting battery 
7÷65Ah/12V (SLA) 
The BAT output current 
20A max. 
The BAT output voltage 
13,8V DC max. 
Battery output protection against short-circuit and 
reverse polarity connection 
(19 mm) - 25A time delay fuse 
Optical indication of operation 
ALARM LED 
Acoustic indication of operation 
Piezoelectric indicator ~75dB /0,3m 
ALARM – technical output of collective failure indication 
Relay type: 1A@ 30VDC/50VAC 
 Mechanical parameters (Table 3). 
Dimensions 
W=108, W
1
=90, H=38, L=80 [+/- 2mm] 
Net/gross weight 
0,15kg / 0,18kg 
Enclosure 
ABS, color RAL 9005, black 
Connectors 
PSU inputs: Φ0,5÷3,2 (AWG 24-8) 0,5-4mm
2
The BAT output: Φ0,5÷3,2 (AWG 24-8) 0,5-4mm
2
The ALARM output: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2 