User Instructions
6
PR4 - T1 to T2 time deactivation delay with resetting T1 time– single cycle.
The "REL" relay is activated
automatically after switching on the
power for the T1 time period. Then, the
"REL" relay is deactivated for the T2
time period. Once the countdown of the
T2 time is finished, the "REL" relay is
activated again. This mode is
maintained until the power is
disconnected.
The „S” triggering signal (rising
edge) during the countdown of the T1
time resets and restarts the T1 countdown process.
PR5 - Activation delay with increasing T2 activation time with Ts time – cyclic.
The countdown of the T1 time takes
place automatically after switching on
the power. Then, the "REL" relay is
activated for the T2 time period. This
mode is repeated cyclically.
In case of the „S” signal (level)
during the countdown of the T2 time,
the countdown is extended by the
duration of the „S” signal.
The countdown is extended only
during the countdown of the T2 time.
PR6 - Deactivation delay with increasing T2 deactivation time with Ts time – cyclic.
The countdown of the T1 time takes
place automatically after switching on
the power. Then, the "REL" relay is
deactivated for the T2 time period. This
mode is repeated cyclically.
In case of the „S” signal (level)
during the countdown of the T2 time, the
countdown is extended by the duration
of the „S” signal.
The countdown is extended only
during the countdown of the T2 time.
PR7 – Bistable mode.
In case of the „S” triggering signal
(rising edge), the REL relay is
immediately switched into opposite
state.