6. Timer programs.
PR0 - Permanent on or off.
In this mode, press the
"OK" button to permanently
switch on or off the relay.
The relay state is
remembered when power is
disconnected and it is
immediately restored when
switched on.
PR1 - T1 time activation delay with locking option single cycle.
The countdown of the T1 time takes
place automatically after switching on
the power. Then, the "REL" relay is
activated. This mode is maintained until
the power is disconnected.
In the case of the S triggering
signal (rising edge) during the
countdown of the T1 time, the module
will lock and the relay will not be
activated.
PR2 - T1 time deactivation delay with locking option single cycle.
The "REL" relay is activated
automatically after switching on the
power for the T1 time period. Once the
countdown of the T1 time is finished, the
"REL" relay is disconnected. This mode
is maintained until the power is
disconnected.
In case of the S” triggering signal
(rising edge) during the countdown of
the T1 time, the module will lock and the
relay will not be deactivated.
PR3 - T1 to T2 time activation delay with resetting T1 time single cycle.
The countdown of the T1 time takes
place automatically after switching on
the power. Then, the "REL" relay is
activated for the T2 time period. Once
the countdown of the T2 time is finished,
the "REL" relay is disconnected. This
mode is maintained until the power is
disconnected.
The S” triggering signal (rising
edge) during the countdown of the T1
time resets and restarts the T1
countdown process.