Operating instructions
3
Technical parameters
Power supply voltage
230V AC, 50 Hz (-15%/+10%)
Transformer TR 80 VA
Output voltage Uout
*12.8 V ÷ +13.8 V DC
13.8 V DC – rated
(13.4 V DC @ 3A )
Output current Iout Imax – 3A (const.)
Power 42 W max
SCP short-circuit protection
I-st grade - 200% ÷ 250%
of supply power – limitation
of current and/or fuse failure in the battery circuit
(fuse-element replacement required)
II – nd. grade - 110% ÷ 150% (@25ºC÷65ºC)
of supply
power – current limitation with the PTC automatic
fuse, manual restart (disconnection of the DC output
circuit)
OLP overload protection
110% ÷ 150% (@25ºC÷65ºC) of
supply
power –
current limitation with the PTC automatic fuse, manual
restart (disconnection of the DC output circuit)
Battery excessive discharge protection
Uout < 10V
(±5%)
Battery charging current
Iacc (max) = 1.6 A @ Iout =0A
0.7 A / 24h (Iśr. /24h)
F2 Fuse in the transformer primary circuit
T 630 mA
(250 V)
Transformer primary circuit current - max
420 mA @ 3 A
(-15%, + 10%)
Transformer thermal protection 130
o
C
F1 Fuse in the battery circuit F 5A
Battery 17 Ah/12V SLA
TAMPER output service reliability - max 500 mA @ 30 V DC max
Enclosure IP IP 20
Operating temperature - 10
o
C ÷ 40
o
C
Relative humidity - max 90 [%] max
Dimensions (WxHxD)
235 x 305 x 98 (90 + 8)
[±2] [mm]
Weight
3.5 kg net
3.6 kg gross
* value dependent on the load current in buffer operation
Tab. 1 - Power pack technical parameters.
Figure 2. Current and voltage characteristics of the power pack.
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 3,2 3,4 3,6 3,8 4
12,8
12,9
13
13,1
13,2
13,3
13,4
13,5
13,6
13,7
13,8
Diagram Uout(Io)
Uwy
I[A]
U[V]