Data Sheet

Table Of Contents
Junction boxes
AWOZ-225S v.1.0/
Distribution Junction Box with 2x0,375A fuse
IV
CODE:
NAME:
DESCRIPTION
The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire
resistance according to the DIN 4102-12 standard, where the uninterruptible power supply or transmission of the signal in case of fire is
required.
The junction box is designed to guarantee the mechanical ability to keep the cable routes capable of guaranteeing the
uninterruptible power supply and transmission of telecommunication signals in the fire zone.
The junction box can be used for power supply of fire protection equipment, such as ventilators and smoke vents, fire alarm
control panels, emergency warning systems, etc.
The junction box is fitted with separate terminals for connecting the signal line input, signal line output and the indicator or
another device via the fuse. The enclosure s equipped with mounting sleeves to mount the optical - acoustic indicator.
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail:sales@pulsar.pl
Pulsar
®
EN**
TECHNICAL PARAMETERS
Voltage
125V AC max
Output current
2x0,375 A
Diameter of installation cable
Max. 10mm
Cross-section of the cable
Max. 2,5mm
2
Protection class
IP20
Enclosure
DC01 1mm steel plate, color RAL 3001 (red)
Dimensions
120 x 120 x 37 [mm] (WxHxD)
Mounting
100mm Φ5,5 mm
Net/gross weight
0,48kg /0,52kg
Certificates, declarations,
warranty
National Technical Assessment
CNBOP-PIB-KOT-2019/0109-3704
National assessment and verification of constancy of
performance CNBOP-PIB 063-UWB-0174
RoHS, 3 year from the production date
+Uz2
+Uz1
+Uz2
+Uz1
+Uz2
+Uz1
0,375A
0,375A
(-)
D
(-)
D
(-)
D
+Uz, (-) - power lines
D - signal line

Summary of content (1 pages)