Data Sheet
Table Of Contents
Junction boxes
AWOZ-225P v.1.0/
Junction box with 2x0,375A fuse
IV
CODE:
NAME:
DESCRIPTION
The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire
resistance according to the DIN 4102-12 standard, where the uninterruptible power supply or transmission of the signal in case of fire is
required.
The junction box is designed to guarantee the mechanical ability to keep the cable routes capable of guaranteeing the uninterruptible
power supply and transmission of telecommunication signals in the fire zone.
The junction box can be used for power supply of fire protection equipment, such as ventilators and smoke vents, fire alarm control
panels, emergency warning systems, etc.
The junction box is fitted with separate terminals for connecting the signal line input, signal line output and the indicator or another device
via the fuse.
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail:sales@pulsar.pl
Pulsar
®
EN**
TECHNICAL PARAMETERS
Voltage
125V AC max
Output current
2 x 0,375 A
Diameter of installation cable
Max. 10mm
Cross-section of the cable
Max. 2,5mm
2
Protection class
IP20
Enclosure
DC01 1mm steel plate, color RAL 3001 (red)
Dimensions
122 x 142 x 30 [mm] (WxHxD)
Mounting
76mm Φ5,5 mm
Net/gross weight
0,61kg /0,65kg
Certificates, declarations,
warranty
National Technical Assessment
CNBOP-PIB-KOT-2019/0109-3704
National assessment and verification of constancy of
performance CNBOP-PIB 063-UWB-0174
RoHS, 3 year from the production date
+Uz2
+Uz1
+Uz2
+Uz1
+Uz2
+Uz1
0,375A
0,375A
(-)
D
(-)
D
(-)
D
+Uz, (-) - power lines
D - signal line