Owner manual

104
14.5 Coils
Coils are discrete, single bit outputs like the ALARM OUTPUT and DIGITAL OUTPUT.
Notes:
Read only.
The coil information is packed as 8 coils per byte.
Coils are accessible through Function Code 0x01.
The requested value is returned in the least most significant bit.
Function Address DDE Ref. Purpose Data Format
Read (0x01) 0x0000 000001 Alarm Output Bit(0x01 = On)
Read (0x01) 0x0001 000002 Digital Output Bit(0x01 = On)
14.6 Input Bits (1x references)
Input Bits are discrete, single bit inputs such as the keyboard KEYS, LEAK DETECTION, LEVEL
INPUT and THERMOSTAT inputs.
Notes:
Read only.
The input information is packed as 8 input bits per message byte.
Input Bits are accessible through Function Code 0x02.
The requested value is returned in the least significant bit.
Function Address DDE Ref. Purpose Data Format
READ (0x02) 0x0000 100001 Key Pad Input: START/STOP Bit(0x01=On)
READ (0x02) 0x0001 100002 Key Pad Input: BATCH Bit(0x01=On)
READ (0x02) 0x0002 100003 Key Pad Input: UP Bit(0x01=On)
READ (0x02) 0x0003 100004 Key Pad Input: MENU Bit(0x01=On)
READ (0x02) 0x0004 100005 Key Pad Input: CALIBRATE Bit(0x01=On)
READ (0x02) 0x0005 100006 Key Pad Input: DOWN Bit(0x01=On)
READ (0x02) 0x0006 100007 Key Pad Input: UNITS Bit(0x01=On)
READ (0x02) 0x0007 100008 Key Pad Input: MODE Bit(0x01=On)
READ (0x02) 0x0008 100009 Key Pad Input: ENTER Bit(0x01=On)
READ (0x02) 0x0009 100010 Digital Input: LEAK DETECT
(J4-3, J4-4)
Bit(0x01=On)
READ (0x02) 0x000A 100011 Digital Input: LEVEL INPUT
(J4-5, J4-6)
Bit(0x01=On)
READ (0x02) 0x000B 100012 Digital Input: MOTOR
THERMOSTAT (J10-3, J10-4)
Bit(0x01=On)
READ (0x02) 0x000C 100013 Encoder: Channel B Bit(0x01=On)
READ (0x02) 0x000D 100014 Encoder: Channel A Bit(0x01=On)
READ (0x02) 0x000E 100015 Digital Input: Tachometer
(J10-1, J10-2)
Bit(0x01=On)