Manual

36
4. The display prompts if the alarm relay should be triggered.
LEAK DETECTION
ALARM RELAY? NO
or
LEAK DETECTION
ALARM RELAY? YES
Press [ENTER] to accept the default of NO. If you want the alarm relay to active if a leak is detected,
press [UP] to scroll to {YES} and press [ENTER]. The display returns to the {MENU / LEAK
DETECTION} screen.
7.2.5 Level Switch Failure Set Up
This sub-menu allows the user to configure the DLC – XP to interact with a single point level sensor.
You can program one of the following responses:
Shut the motor off,
Trigger the alarm relay'
Shut the motor off and trigger the alarm relay.
The level sensor must be a dry contact type. Refer to Section 5 – Installation: Low Voltage Input
Connections.
1. Press the [MENU] key and [UP] four times until the {–MENU– / LEVEL SWITCH} screen is
displayed.
–MENU–
LEVEL SWITCH
Press [ENTER] to continue to program the Level Switch sub-menu.
2. The low level input can be configured as {INACTIVE}, if the system will not use a level sensor or as
{ACTIVE} if the system is going to use a level sensor.
LEVEL SWITCH
INACTIVE
Pressing [ENTER] when {INACTIVE} is displayed will cause the screen to return to the {–MENU–
/ LEVEL SWITCH} screen. Skip to step 9.
Pressing [UP] when {INACTIVE} is displayed will cause the screen to display {ACTIVE}.
Continue with step 3.
3. The low level input can be configured as {ACTIVE}, if the system will use a level sensor.
LEVEL SWITCH
ACTIVE
Pressing [ENTER] when {ACTIVE} is displayed will open the {LEVEL SWITCH / DRUM
LEVEL} screen.
LEVEL SWITCH
DRUM LEVEL
or
LEVEL SWITCH
START/STOP
Press [UP] to scroll to the next option {LEVEL SWITCH / START/STOP}
Press [ENTER] to make your selection and the following screen is displayed.
LEVEL SWITCH
NORMALLY OPEN
4. The input can be configured as {NORMALLY OPEN} by pressing [ENTER], or press [UP] to scroll
to the next input option (i.e., Normally Closed).
LEVEL SWITCH
NORMALLY CLOSED
Press [ENTER] to accept the desired configuration.