Manual

Factory Re-initialization is typically not required. When re-
initializing your MPC, all of the system settings and calibration
information will be overwritten by the original factory default
settings. The controller must be re-configured and re-calibrated to
your specifications.
A Factory Re-initialization should be performed only if there is reason to
believe that the internal MPC memory has become corrupted. The
condition usually manifests itself with inconsistent or erratic operation
often associated with meaningless characters on the display, or
exaggerated numerical values.
Factory Re-Initialization:
1. Press the MENU key to access the System Setup Menu
-MENU-
CALIBRATION
2. Press the UP arrow key to display
-MENU-
SYSTEM SETUP
3. Press the ENTER key
SYSTEM SETUP
SECURITY
4. Press the UP arrow key twice to display
SYSTEM SETUP
FACTORY INIT
5. Press the ENTER key
PRESS ENTER
TO FACTORY INIT
6. Press the ENTER key
ARE YOU SURE?
YES=ENTER NO=MENU
7. Press the ENTER key
RESETTING PUMP
TO FACTORY INIT