39
Param.
Name Description Range Typical Note
85 Motor Rated Speed Nameplate RPM Rating 300 – 65,000
RPM
1800 RPM
86 Motor Rated Amps Nameplate FLA Rating 0.0 – 480 Amps Various 1
87 Motor Rated Volts Nameplate Voltage Rating 0 – 600 Volts 230 VAC
88 Motor Base Frequency Nameplate Frequency 25 – 500 Hz 50 or 60 Hz
91 Motor Cosine Phi Nameplate Cosine Phi 0.4 – 0.99 Approx 0.8 2
81 Invoking this parameter begins the auto-calibration routine
NOTES:
1. FLA = Full Load Amps
2. The Cosine Phi is also known as the Power Factor, this will sometimes be on the nameplate as
“PF”. If the Power Factor is given as a %, always use the decimal equivalent (for example a power
factor of 84% would be entered as 0.84) If the Cosine Phi is not provided by the motor manufacturer,
one of the following formulas may be used.
732.1
746
)2(
sincos)1(
1
×××
×
=Φ
=Φ
CurrentMotorVoltageMotorEfficiencyMotor
HPMotor
COS
CurrentMotor
CurrentgMagnetizin
COS
After all of the Parameters have been entered, the drive needs to perform an auto-calibration routine
(Parameter 81). This calibration routine will take several seconds to complete. The user may use the Menu
Key to back up and/or out of the calibration any time prior to the auto calibration. The motor, and therefore
the pump, will not run during this auto-calibration procedure.