Troubleshooting guide
19
8.1.3 Flow Method
SET STROKE 50%
FLOW = 0.0000 GPH
1. You do not have to adjust the actual stroke setting of the pump
2. Use the UP and DOWN arrow keys and the ENTER key to input the desired flow rate (in
gallons or liters per hour, dependent on MPC setup). This should be the flow rate
expected when the pump is set to 50% stroke length setting.
3. Press ENTER to proceed
SET STROKE 100%
FLOW = 000.00 GPH
4. You do not have to adjust the actual stroke setting of the pump
5. Use the UP and DOWN arrow keys and the ENTER key to input the desired flow rate (in
gallons or liters per hour, dependent on MPC setup). This should be the flow rate
expected when the pump is set to 100% stroke length setting.
6. Press ENTER to proceed
PUMP FLOW
CALIBRATED
7. Pump flow calibration is complete
8. Press the MENU key three times to exit back to the main operating screen.