Troubleshooting guide

17
8.1.1 To Start Calibration
1. The starting display will be:
SETPT XX.XXX
FLOW XX.XXX
2. Press the MENU key
-MENU-
CALIBRATION
3. Press the ENTER key
CALIBRATION
PUMP FLOW
4. Press the ENTER key
CALIBRATION
“VOLUME”
5. To perform the Volume Method, press the ENTER key and go to Section 8.1.2
6. To perform the Flow Method, press the UP arrow key
CALIBRATION
“FLOW”
7. Press the ENTER key and go to Section 8.1.3
If you receive the following message during the Volume calibration:
STROKE LENGTH OUT
OF RANGE
Verify that the manually set stroke length is at the correct position, either 50% or 100%.