Troubleshooting guide

12
6. Start Up and Operation
6.1 Overview
Once all electrical connections have been made, your MPC is ready for Start-up. The following sections
detail the procedures required to complete the MPC start up.
WHEN POWER IS SUPPLIED TO THE UNIT, LINE VOLTAGE IS PRESENT WITHIN THE MPC
ENCLOSURE EVEN WHEN THE MOTOR IS OFF.
DURING START-UP, IT IS NECESSARY TO RUN THE PUMP MOTOR. THIS WILL CAUSE FLUID TO
DISCHARGE FROM THE PUMP
. YOU ARE RESPONSIBLE FOR SAFELY DIVERTING FLOW FROM THE
PUMP DURING START
-UP AND CALIBRATION.
6.2 Keypad/Lamp Operation
Key Function Description
Motor On/Off Press to start pump, press again to stop pump
Auto/Manual
Press to toggle between automatic operation and manual
control of the pump
Menu
Press to adjust controller settings, to exit the menu system,
to move cursor back when entering values, or to step back to
higher level menus
Enter
Press to accept changes in menus, to move cursor forwards
when entering values, and to access lower level menus.
Also used to toggle between pump output display options
while in operating mode (% flow, spm, gph, etc)
Arrow Up
Press to adjust values upwards, and to scroll through menu
options
Arrow Down
Press to adjust values downwards, and to scroll through
menu options
Lamp Color Description
Green, Amber,
Red, Off
Off = Motor off Green = Motor on
Amber = Remote standby Red (blinking) = Error
Green, Off Green = Manual Control Off = Automatic Control
Table 3 – Keypad and Lamp Operation
MANUAL
ON