24V, 3.3A, SINGLE PHASE INPUT
8. EFFICIENCY AND POWER LOSSES
AC 100V AC 120V AC 230V
Efficiency typ. 86.4% 88.0% 89.8% at 24V, 3.3A
Average efficiency
*)
typ. 87.4% 88.4% 87.7% 25% at 0.83A, 25% at 1.65A,
25% at 2.5A. 25% at 3.3A
Power losses typ. 1.0W 1.1W 1.8W at 24V, 0A
typ. 5.4W 4.9W 5.9W at 24V, 1.65A
typ. 12.5W 11.1W 9.1W at 24V, 3.3A
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 8-1 Efficiency vs. output current at 24V,
typ
Fig. 8-2 Losses vs. output current at 24V, typ.
Efficiency
0.5 1.0 3.5A
86
87
88
89
Output Current
90
91%
85
2.0 3.01.5 2.5
(
a
)
(
b
)
(
c
)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Power Losses
0 0.5 3.5A
0
2
4
6
8
10
12W
1.01.52.02.53.0
Output Current
(
a
)
(
b
)
(
c
)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Fig. 8-3 Efficiency vs. input voltage at 24V,
3.3A, typ.
Fig. 8-4 Losses vs. input voltage at 24V, 3.3A,
typ.
Efficiency
85 120
155
190 225 260Vac
85
86
87
88
Input Voltage
89
90
91%
Power Losses
0
3
6
9
12
15
18W
85 120
155
190 225 260Vac
Input Voltage
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.