Datasheet
CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 38ms 60ms 244ms at 24V, 1.65A, see Fig. 7-1
min. 29ms 45ms 200ms at 24V, 1.65A, see Fig. 7-1
typ. 19ms 29ms 120ms at 24V, 3.3A, see Fig. 7-1
min. 15ms 23ms 95ms at 24V, 3.3A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
25
50
75
100
225ms
85 120 155 190 230Vac
Input Voltage
125
150
175
Hold-up
Time
200
24V, 3.3A, min.
24V, 3.3A, typ.
24V, 1.65A, min.
24V, 1.65A, typ.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/24