Datasheet

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V
Adjustment range min. 24-28V guaranteed
max. 30V
**)
at clockwise end position of potentiometer
Factory settings typ. 24.1V ±0.2%, at full load, cold unit,
Line regulation max. 50mV 90-300Vac
Load regulation max. 100mV static value, 0A Æ 3.3A; see Fig. 6-1
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 3.3A at 24V, ambient temperature <60°C, see Fig. 6-1
nom. 2.5A at 24V and 70°C ambient temperature
nom. 2.7A at 28V, ambient temperature <60°C, see Fig. 6-1
nom. 2.1A at 28V and 70°C ambient temperature
Reduce output current linearly between +60°C and +70°C
Output power nom. 80W continuously available
Overload behavior continuous current see Fig. 6-1
Short-circuit current min. 4A
*)
load impedance <250mOhm, see Fig. 6-1
max. 8A
*)
load impedance <250mOhm, see Fig. 6-1
Output capacitance typ. 1 450μF included inside the power supply
*) Discharge current of output capacitors is not included.
**) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 28.5V.
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
0
04
4
8
12
28V
16
20
24
7A621 3 5
Adjustment
Range
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
abc
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/24