Datasheet

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V ±10%, Wide-range input
Mains network systems TN, TT or IT
AC input range min. 90-264Vac
85-90Vac
264-300Vac
continuous operation
short-tem or with reduced output current
max. 500ms
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 75Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 58Vac steady-state value, see Fig. 3-1
External input protection See recommendations in chapter 22.3.
AC 100V AC 120V AC 230V
Input current typ. 1.48A 1.23A 0.68A at 24V, 3.3A, see Fig. 3-3
Power factor
*)
typ. 0.62 0.61 0.56 at 24V, 3.3A, see Fig. 3-4
Crest factor
**)
typ. 3.1 3.2 4.0 at 24V, 3.3A
Start-up delay typ. 95ms 95ms 95ms see Fig. 3-2
Rise time typ. 18ms 29ms 56ms at 24V, 3.3A const. current load,
0mF load capacitance, see Fig. 3-2
typ. 35ms 52ms 92ms at 24V, 3.3A const. current load,
3.3mF load capacitance
Turn-on overshoot max. 400mV 400mV 400mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges Fig. 3-2 Turn-on behavior, definitions
Turn-on
(85)90
max.
500ms
V
IN
P
OUT
300Vac264
Shut-down
Rated Input
Range
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
0.5 1.51.0 2.0 2.5 3.0 3.5A
0
0.3
0.6
0.9
1.2
1.5
1.8A
Output Current
Input Current, typ.
(a) 100Vac
(b) 120Vac
(c) 230Vac
(
a
)
(
b
)
(
c
)
Power Factor, typ.
0.5 1.0 1.5 2.0 3.5A
0.40
0.45
0.50
0.55
0.60
0.65
Output Current
2.5 3.0
(a) 100Vac
(b) 120Vac
(c) 230Vac
(
a
)
(
b
)
(
c
)
Jul. 2015 / Rev. 2.0 DS-CS3.241-EN