Datasheet
YR20.246
Y-Series
24-28V, 20A, DUAL REDUNDANCY MODULE
13. ENVIRONMENT
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F)
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Humidity
**)
5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal
***)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
***)
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 13-2
Altitude de-rating 1.25A/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 13-2
Over-voltage category not applicable The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
Degree of pollution 2 EN 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation.
Fig. 13-1 Output current vs. ambient temp. Fig. 13-2 Output current vs. altitude
Allowed Output Current
0
0 2000 4000
6000m
5
10
15
20
24
32.5A
n
o
r
m
a
l
m
o
d
e
Altitude
A... Tamb < 45°C
B... Tamb < 70°C
A
B
s
h
o
r
t
t
e
r
m
(
<
5
s
)
Allowed Output Current
0
-40 0 20 45
70°C
5
10
15
20
24
32.5A
-25
n
o
r
m
a
l
m
o
d
e
Ambient Temperature
s
h
o
r
t
t
e
r
m
(
<
5
s
)
Jul. 2017 / Rev. 1.4 DS-YR20.246-EN All parameters are typical values specified at 24V, 20A output current, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/19