Datasheet
YR20.242
Y-Series
12-28V, 20A, DUAL REDUNDANCY MODULE
6. TERMINALS AND WIRING
Input and Output
Type Screw termination, IP20 Finger safe construction.
Suitable for field installation.
Solid wire max. 6mm
2
Stranded wire max. 4mm
2
American Wire Gauge AWG 20-10
Max. wire diameter 2.8mm (including ferrule)
Wire stripping length 7mm / 0.275inch
Screwdriver 3.5mm slotted or Pozidrive No 2
Recommended tightening torque 0.8Nm, 7lb.in
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Screws of unused terminal compartments should be securely tightened.
e) Ferrules are allowed.
7. FUNCTIONAL DIAGRAM
Fig. 7-1 Functional diagram
+
-
+
-
+
-
Input 1
control
control
Input 2
Chassis
Ground
Output
Jul. 2017 / Rev. 1.3 DS-YR20.242-EN All parameters are typical values specified at 24V, 20A output current, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/17